5X00226G04 | Emerson Ovation 16CH HART Analog Output Module
Product Introduction
5X00226G04 is original Westinghouse/Emerson Ovation DCS 16-channel HART analog output card, dedicated to output 4~20mA analog control signal for field positioning valve, actuator, transducer and HART intelligent instruments, hot-swappable rack installation, supporting full HART multi-drop digital communication, matched dedicated Ovation terminal base for field wiring, widely equipped on thermal power, chemical Ovation control cabinet.
Description
Part Code Definition
5X00226G04: full factory ordering part number, G04 stands for hardware revision version; no interchange alternative part codes, fixed model for 16-channel HART AO module under Ovation platform.
Technical Specifications
Backplane power supply: 24VDC from Ovation rack backplane, module power consumption ≤7.2WChannel configuration: total 16 independent isolated AO channels, each channel standard 4~20mA analog output + HART digital superimposed signalSingle channel load resistance: max 750Ω for 4-20mA drive; HART communication impedance match compliant with IEC61158 standardOutput precision: full scale accuracy ±0.05%FS, 16-bit D/A conversion resolutionAmbient condition: operating -40℃~+70℃, storage -40℃~+85℃, 5%~95%RH non-condensing, vibration resistant conform IEC60068Dimension & Weight: standard single-slot Ovation card 152×82×215mm, net weight≈0.62kgIsolation design: channel-to-backplane galvanic isolation 1500VDC, inter-channel partial isolation for anti-interference
Interface & Communication Layout
Rear golden finger: Ovation proprietary high-speed backplane bus, real-time data exchange with Ovation controllerFront side: docking port for Ovation dedicated AO terminal base to connect field HART equipment cableFront panel LED indicators: POWER, RUN, FAULT, 4 group channel status LED for power status, running state, module fault and channel abnormal alarmBuilt-in HART master chip, each channel supports independent HART polling, reading instrument tag, calibration data, equipment fault code remotely via DCS workstation
Core Functions
Convert digital control command from Ovation controller into standard 4~20mA current signal to drive field regulating valves and actuators to complete closed-loop process controlTwo-way HART communication: downward send remote calibration, parameter setting command to HART smart devices; upward upload instrument model, fault code, process auxiliary variable to DCS systemFull channel self-diagnosis: auto detect output open-circuit, short-circuit, over-load failure, alarm and record fault log on Ovation operator stationHot swap maintenance: replace module online without cabinet power off, unaffected operation of other intact channels, online download configuration via Ovation engineering software without system shutdown
Application Scenarios
Coal-fired power plant boiler feedwater valve, flue gas damper, steam regulating valve output control; chemical plant reactor feeding valve, pressure regulating actuator signal output; thermal power circulating water, desulfurization denitration HART intelligent instrument control cabinet spare replacement
Operation & Maintenance Notes
Must install on specified Ovation single I/O slot and matching original dedicated terminal base; confirm slot coding before plug-in to avoid hardware damageField signal cable separate from high-voltage power cable during wiring to avoid EMI causing output drift and HART communication dropoutRegularly check front panel fault LED and DCS system fault log for over-load or short-circuit troubleshooting; tighten terminal wiring periodically to prevent poor contactWhen using HART multi-drop bus wiring, strictly control total loop load resistance to ensure stable digital communication of multiple field instruments on single channel