5X00622G01 | Emerson Ovation 16CH RTD Temperature Input Module
Product Introduction
5X00622G01 is original Emerson(Westinghouse legacy) Ovation DCS dedicated 16-channel RTD analog input module, designed for field resistance temperature detector signal acquisition, converts RTD resistance variation into digital data for Ovation controller processing, hot-swappable standard rack installation, widely used in power plant boiler, turbine temperature monitoring, passed UL/CE/CSA industrial certification.
Description
Part Code Definition
5X00622G01:complete factory ordering part number, fixed model for 16-channel RTD input card under Ovation platform, no alternate base part series.
Technical Specifications
Power supply:24VDC backplane powered, module power consumption ≤10WChannel resource:16 isolated independent RTD input channels, compatible 2-wire/3-wire/4-wire wiring modeSupported sensor:Pt100/Pt500/Pt1000, Cu50/Cu100, Ni120 mainstream RTD typesMeasurement range:-200℃ ~ +850℃, typical measuring accuracy ±0.1℃, 16-bit ADC conversion resolutionEnvironment parameter:operation -40℃~+70℃, storage -40℃~+85℃, 5%~95%RH non-condensing, anti-vibration comply IEC60068 standardDimension & Weight:standard Ovation single-slot size 160×80×220mm, net weight approx 500gIsolation design:channel-to-channel & channel-to-backplane galvanic isolation, anti-field interference
Interface & Communication Layout
Rear golden finger backplane bus: native Ovation system high-speed bus, real-time data interaction with Ovation controllerFront terminal base docking port: matches Ovation standard terminal base for field RTD sensor wiring connectionFront panel LED indicators: POWER, RUN, FAULT, CHANNEL status lamp for power, running, module fault and single-channel failure prompt
Core Functions
Full-range temperature acquisition of multiple RTD sensors, automatic lead wire resistance compensation to eliminate wiring error influenceBuilt-in channel-level self-diagnosis, auto detect open circuit/short circuit of field RTD wiring and upload fault alarm to DCS workstationHot swap maintenance without cutting cabinet power, replacement won’t interrupt normal operation of remaining channels and whole DCS systemUnified configuration via Ovation engineering software, online parameter modification of sensor type, measuring range without system halt
Application Scenarios
Coal-fired power plant boiler wall temperature, steam pipe temperature, turbine bearing temperature collection; thermal power auxiliary system water tank/air duct temperature monitoring; petrochemical refining furnace and reactor temperature measurement cabinet spare parts replacement.
Operation & Maintenance Notes
Install only on standard Ovation I/O rack single slot, confirm backplane slot coding before insertion to avoid mismatched slot damageSeparate RTD weak signal cable from high-power AC power cable during field wiring to reduce EMI interference causing measuring driftCheck front panel fault indicator and DCS fault log periodically for abnormal channel troubleshooting; confirm module front terminal wiring tightness regularly
Get a Quote