SE4006P2 KJ3241X1-BK1 | Emerson DeltaV S-series Serial Interface Module
June 03, 2026

SE4006P2 KJ3241X1-BK1 | Emerson DeltaV S-series Serial Interface Module

Product Introduction SE4006P2(KJ3241X1-BK1,alternative PN:12P4710X062/12P4710X082) is S-series simplex serial communication interface card for DeltaV DCS, dedicated for serial protocol docking between DeltaV controller and third-party field equipment, preloaded Modbus RTU/ASCII driver without extra gateway device. Supports single-card standalone or 1+1 redundant hot backup configuration, hot-swappable on standard DeltaV I/O rack, realizes transparent data read-write between DCS and external serial devices, compatible with S/VE/CE series DeltaV controller backplane bus. Matched terminal block model: KJ4006X1-BD1(D4 coding terminal base).

Description

Part Code Definition

SE4006P2:S-series serial interface internal model code
KJ3241X1-BK1:official ordering part number & hardware revision mark
12P4710X series:factory spare alternate part numbers

Technical Specifications

Backplane power:12VDC from LocalBus, rated operating current 300mA, typical power consumption 3.6W
Serial port allocation:2 independent isolated serial ports, total 32 configurable data mapping points(16 points per channel)
Port electrical standard:each port configurable as RS232 / RS422 half-duplex / RS422 full-duplex / RS485, galvanic isolation between two ports and system bus, isolation voltage 1500VDC
Baud rate range:300~115200bps full-range adjustable via DeltaV engineering software
Ambient parameter:operating -40℃~+70℃, storage -40℃~+85℃, 5%~95%RH non-condensing, anti-vibration 0.5g@10~150Hz
Dimension & Weight:125×102×52mm, net weight≈0.2kg, single-slot rack installation

Interface & Communication Layout

Rear golden finger LocalBus connector for data interaction with DeltaV rack backplane and upper controller
Front terminal wiring port matches D4 coded KJ4006X1-BD1 terminal base for field serial cable wiring
Front panel status LED:POWER, RUN, COMM1, COMM2 four indicator lamps for power, running and dual-port communication diagnosis
Built-in onboard firmware storage, pre-installed Modbus driver, supports user-defined custom serial protocol driver download

Core Functions

Collect real-time data from third-party serial equipment (MCC 马达控制柜、在线分析仪、第三方 PLC、称重仪表、变频设备等) and upload to DeltaV DCS database, issue DCS control command downwards to peripheral devices via serial bus
Channel-level communication fault self-diagnosis, automatically record communication interruption, baud rate mismatch and wiring failure logs, upload fault information to DeltaV operation station
Redundant pairing installation supports bumpless automatic master-slave switchover when main card communication failure occurs, no interruption of serial data transmission
Plug-and-play module identification via DeltaV software, online download protocol configuration without stopping system operation

Application Scenarios

Petrochemical plant MCC motor centralized monitoring, refining unit online analyzer data access, chemical workshop third-party PLC system interconnection, thermal power auxiliary water system frequency converter signal acquisition, old factory equipment transformation serial communication expansion cabinet spare replacement

Operation & Maintenance Notes

Must use matched D4 coding terminal base KJ4006X1-BD1 for field wiring to prevent wrong slot installation
Separate serial signal cable from high-current AC power cable to avoid EMI interference causing communication packet loss
Cut off corresponding rack slot power supply before hot-swap replacement; regularly check front panel communication LED and system fault log for abnormal communication troubleshooting
Redundant paired two modules install on adjacent rack slots with independent terminal bases respectively, separate field wiring circuit for dual-port redundancy