EMERSON 1C31179G01 Ovation RTD Temperature Input Module
June 03, 2026

EMERSON 1C31179G01 Ovation RTD Temperature Input Module

Product Introduction 1C31179G01 is Emerson Ovation RIO link master module inherited from Westinghouse design, the core communication bridge between Ovation main controller backplane and distributed remote I/O racks. It processes inter-rack bus protocol conversion, realizes bulk analog/digital I/O data collection & forwarding, widely used in thermal power, petrochemical DCS remote cabinet expansion and spare replacement.

Description

Part Code Definition

1C31xxx: Ovation compact remote I/O series prefix

179: exclusive code for RIO link controller master card

G01: first generation hardware revision

Technical Specifications

Backplane 5VDC power supply, typical power consumption 5.2W;

Dedicated RIO field bus port based on RS485 differential transmission, max bus length 1200m, up to 31 slave remote I/O racks cascaded;

Bus communication rate fixed 19200bps with built-in hardware CRC error check;

1500VAC isolation between field bus circuit and system internal backplane bus;

Working ambient: -40℃~+70℃, 5%~90%RH non-condensing, supports hot plug in standard Ovation rack;

Dimension:45×158×272mm, net weight approx 0.37kg.

Interface & Communication Layout

Rear golden finger connects chassis backplane for Ovation internal control bus data exchange;

Front terminal port for shielded RS485 trunk wiring to subordinate remote I/O cabinets;

Front panel LED indicators: RUN normal operation lamp, FAULT module failure lamp, COM bus communication status lamp.

Core Functions

Master scheduling of entire remote I/O bus, cyclic polling all downstream slave I/O modules;

Forward field collected AI/DI data upward to Ovation main controller, distribute DCS downlink DO/AO control commands to remote I/O racks;

Full bus fault diagnosis: bus short/open, slave rack offline, module abnormal, fault codes automatically uploaded to DCS for system alarm record;

Online bus node address & communication parameter configuration via Ovation engineering software without module offline;

Single slave rack fault isolated without affecting operation of other remote stations on the same bus.

Application Scenarios

Thermal power plant boiler auxiliary equipment remote I/O cabinet, turbine auxiliary system distributed signal collection; petrochemical on-site field separation cabinet remote I/O expansion, old DCS renovation spare stocking.

Operation & Maintenance Notes

RIO trunk uses double-core shielded twisted cable, single-point shielding grounded inside main control cabinet;

Install 120Ω terminal matching resistor at the two extreme ends of RS485 bus; separate bus cable from high-power AC cable to eliminate EMI interference;

Regularly inspect terminal tightness and bus online status; replace module when persistent total bus communication breakdown after field wiring troubleshooting.


Get a Quote