Emerson 1C31227G01 | 8-Channel Analog Input Personality Module
Description
Part Code Definition
1C31xxx = Ovation standard remote I/O personality module series;
227 = model code for 8-channel 4-20mA analog input card;
G01 = fixed factory hardware revision version.
Technical Specifications
Backplane powered by rack 5VDC bus, field loop powered or local auxiliary 24VDC optional;
8 fully isolated independent input channels, fixed input range: 4~20mA DC current signal;
A/D conversion resolution:14-bit, full-scale precision ≤±0.15% at 25℃ ambient;
Dielectric isolation: 1500VAC galvanic isolation between channel vs backplane and inter-channels;
Sampling rate: 20Hz (60Hz noise filtering) /25Hz (50Hz noise filtering), CMRR≥120dB, NMRR≥60dB;
Operating environment: -40℃~+70℃, 5%~90%RH non-condensing; supports hot-swap on standard Ovation I/O rack; net weight approx 0.36kg.
Interface & Communication Layout
Rear gold finger docks with corresponding base module to connect rack backplane system bus;
Front screw terminal block for field transmitter shielded cable wiring;
Front panel LED indicators: RUN operating lamp, module fault alarm and channel open-circuit status indication.
Core Functions
Real-time analog signal acquisition & A/D conversion for flow, pressure, temperature transmitters;
Per-channel open-circuit detection, overload protection, single-channel abnormal state no interference to other 7 channels;
Built-in hardware self-diagnosis for module power fault, channel out-of-range, open loop, all fault codes uploaded to Ovation controller automatically;
Support periodic automatic self-calibration triggered by DCS configuration software to maintain long-term measuring accuracy.
Application Scenarios
Boiler feedwater flow, furnace pressure, steam temperature real-time collection in thermal power plants; refining pipeline pressure, tank level, reaction temperature signal acquisition for petrochemical DCS system expansion and spare replacement.
Operation & Maintenance Notes
Field signal wiring adopts shielded twisted-pair cable with single-end shielding grounded inside control cabinet;
Separate analog signal wires from high-power AC cables to avoid electromagnetic interference;
Check terminal fastening tightness and loop current value during regular maintenance; replace module once persistent hardware diagnostic alarm occurs.
Get a Quote