Honeywell 51196654-100
June 01, 2026

Honeywell 51196654-100

Product Introduction The 51196654-100 is a 10‑Slot File Power Supply (CE‑compliant) for Honeywell TDC3000 / Experion PKS Micro TDC chassis. It delivers multi‑rail regulated power to 10‑slot card files, serving as the high‑capacity counterpart to the 5‑slot 51196653‑100.

Description

Model Explanation

  • 51196654: Base part number for TDC3000 10‑slot power supply

  • ‑100: Standard base model (CE‑compliant)

Technical Parameters

  • Device Type: 10‑slot DCS power supply module

  • Compatibility: Honeywell TDC3000, Experion PKS (10‑slot Micro TDC chassis)

  • Input Voltage: 120/240 VAC, 47–63 Hz

  • Input Current: 120 VAC @ 6 A; 240 VAC @ 3 A

  • Output Voltages & Max Current:

    • +5 VDC: 60 A

    • +12 VDC: 20 A

    • −12 VDC: 2 A

    • +27 VDC: 2.4 A

  • Operating Temperature: 0 °C to +60 °C

  • Humidity: 5%–95%, non‑condensing

  • Dimensions: 365 mm × 370 mm × 80 mm

  • Weight: Approx. 4.4 kg

  • Protection: Overvoltage, overcurrent, short‑circuit, thermal overload

Interface & Communication Configuration

  • Input: AC power terminal block (120/240 VAC)

  • Output: Backplane gold finger connector for 10‑slot card file

  • Status Indicators: Power OK, Fault LEDs on front panel

  • Redundancy: Supports hot‑swap redundant parallel operation

Core Functions

  • High‑Capacity Power Distribution: Delivers stable multi‑rail power to ten slots

  • System Reliability: Maintains DCS operation during voltage fluctuations

  • Fault Protection: Shuts down safely on overload/short circuit; triggers alarm

  • Hot‑Swap Support: Allows replacement without system shutdown (redundant configs)

  • Backplane Isolation: Protects modules from power‑line noise and spikes

Application Scope

  • Honeywell TDC3000 / Experion PKS distributed control systems (10‑slot chassis)

  • Process industries: chemical, power generation, oil & gas, refining

  • High‑density DCS cabinets with ten‑slot card files

  • System upgrades, replacements, and spare power supplies

Operation & Maintenance Instructions

  • Install only with system powered off; observe ESD precautions

  • Verify AC input voltage (120/240 VAC) matches module rating before power‑on

  • Check that Power OK LED is lit; Fault LED off during normal operation

  • Periodically clean air vents and connectors; ensure adequate ventilation

  • Avoid overloading; do not exceed ten‑slot configuration

  • For critical systems, use redundant power supplies to minimize downtime


Get a Quote