Honeywell 51196653-100-RP
June 01, 2026

Honeywell 51196653-100-RP

Product Introduction The 51196653-100-RP is a 5‑Slot File Power Supply (Redundant/Replacement Part) for Honeywell TDC3000 / Experion PKS DCS. The suffix ‑RP stands for Replacement Part / Redundant Package, denoting a factory‑certified spare or redundant‑configured unit, functionally identical to the standard 51196653-100 (Rev. C) but marked for spare/redundant use.

Description

Model Explanation

  • 51196653: Base part number for TDC3000 five‑slot power supply

  • ‑100: Standard hardware revision (Rev. C)

  • ‑RP: Replacement Part / Redundant Package (spare/redundant version)

Technical Parameters

  • Device Type: 5‑slot DCS power supply module (spare/redundant)

  • Revision: Rev. C

  • Compatibility: Honeywell TDC3000, Experion PKS (5‑slot card files)

  • Input Voltage: 100–240 VAC, 50/60 Hz

  • Output Voltages & Max Current:

    • +5 VDC: 30 A

    • +12 VDC: 10 A

    • −12 VDC: 1 A

    • +27 VDC: 1.2 A

  • Operating Temperature: 0 °C to +60 °C

  • Humidity: 5%–95%, non‑condensing

  • Dimensions: 366 mm × 370 mm × 55 mm

  • Weight: Approx. 3.8 kg

  • Protection: Overvoltage, overcurrent, short‑circuit protection

Interface & Communication Configuration

  • Input: AC power terminal block (100–240 VAC)

  • Output: Backplane gold finger for 5‑slot card file

  • Status Indicators: Power OK, Fault LEDs on front panel

  • Redundancy: Supports redundant parallel operation (‑RP optimized)

Core Functions

  • Regulated Power Distribution: Delivers stable multi‑rail power to five slots

  • Redundancy‑Ready: Optimized for hot‑swap redundant operation (‑RP feature)

  • Fault Protection: Shuts down safely on overload/short circuit; triggers alarm

  • Hot‑Swap Support: Allows replacement without system shutdown

  • Backplane Isolation: Protects modules from power‑line noise and spikes

Application Scope

  • Honeywell TDC3000 / Experion PKS DCS (5‑slot card file cabinets)

  • Process industries: chemical, power generation, oil & gas, refining

  • Spare parts inventory and redundant system upgrades (‑RP primary use case)

  • Legacy DCS maintenance and emergency replacement

Operation & Maintenance Instructions

  • Install only with system powered off; observe ESD precautions

  • Verify AC input voltage matches module rating before power‑on

  • In redundant configs, ensure both units are synchronized and load‑balanced

  • Check that Power OK LED is lit; Fault LED off during normal operation

  • Periodically clean air vents and connectors; ensure adequate ventilation

  • Store spare (‑RP) units in dry, ESD‑protected environment