Product Specification: X20AI4622 Analog Input Module
Description

Product Specification: X20AI4622 Analog Input Module
1. General Information
Manufacturer: B&R Industrial Automation
Part Number: X20AI4622
Alternative Model: X20cAI4622 (Conformal Coating Version)
Product Type: 4-Channel Universal Analog Input Module
Product Series: B&R X20 Distributed I/O System
Certification: CE, UKCA, ATEX, cULus, KC
Product Status: Mass production active, fully supported
2. Product Overview
3. Technical Specifications
3.1 Analog Input Parameters
Number of Channels: 4 isolated differential analog inputs
Configurable Signal Type: Voltage / Current (software selectable per channel)
Voltage Input Range: ±10 VDC
Current Input Range: 0…20 mA, 4…20 mA
Resolution: 13-bit (including sign bit)
Total Conversion Time: 400 µs for all 4 channels
Input Impedance:
Voltage mode: 20 MΩ
Current mode: 100 Ω
Input Filter: 3rd order low-pass filter, cutoff frequency configurable
Overvoltage Protection: ±30 V maximum
Overcurrent Protection: 50 mA maximum
Common Mode Voltage Range: ±12 VDC
3.2 Accuracy Performance (25°C Ambient)
Full scale gain error: ±0.1%
Offset error: ±0.05%
Full scale gain error: ±0.1%
Offset error: ±0.05%
3.3 Electrical Characteristics
System Bus Interface: X20 backplane bus
Power Consumption:
Bus power: 0.01 W
Internal I/O power: 1.1 W
Isolation: Galvanic isolation between field side, logic circuit and backplane bus
3.4 Physical and Environmental Parameters
Form Factor: Standard X20 slice modular design
Module Width: 12.5 mm
Mounting Method: Installed on X20 bus base module, DIN rail mounting compatible
Matching Bus Base: X20BM11
Matching Terminal Block: X20TB12 (12-pin)
Operating Temperature:
Horizontal installation: -25°C ~ +60°C
Vertical installation: -25°C ~ +50°C
Storage Temperature: -40°C ~ +85°C
Relative Humidity: 5% ~ 95% RH, non-condensing
Vibration and Shock: Compliant with IEC 60068 industrial standard
Protection Grade: IP20 (front panel)
3.5 Indication and Diagnosis
Channel Status LED: 4 individual LEDs for each input channel status
Module Status LED: Power, run and fault state indication
Diagnostic Functions:
Module running and error self-diagnosis
Overvoltage and overcurrent fault detection
Wire break detection under current input mode
Real-time monitoring of channel signal status
4. Key Features
Four independent universal analog input channels, saving cabinet installation space
Software configurable voltage/current mode per channel, flexible for various sensors
13-bit high resolution ensures stable and accurate signal acquisition
Configurable low-pass filter effectively suppresses industrial electromagnetic interference
Complete overvoltage, overcurrent and wire break protection functions
Galvanic isolation design improves system anti-interference and safety
Support hot swap, convenient for on-site maintenance and replacement
Compatible with ATEX hazardous area application requirements
Perfectly matched with B&R Automation Studio for unified configuration and programming
5. Typical Applications
Process automation: Acquisition of pressure, temperature, flow and liquid level transmitter signals
Packaging, textile and material handling machinery analog signal monitoring
HVAC and industrial building automation system sensor collection
Water treatment and environmental protection equipment analog signal acquisition
Automated test bench and measurement system data collection
Chemical, pharmaceutical and other hazardous area on-site signal monitoring
6. Compatibility
Compatible System: All B&R X20 series PLC and controller platforms
Supporting Base Module: X20BM11 standard bus base module
Supporting Terminal Block: X20TB12 12-pin screw terminal block
Programming Software: B&R Automation Studio full configuration and programming support
7. Reliability and After-sales Support
Industrial design for 24-hour continuous long-term operation
Follow B&R official standard warranty policy
Product in continuous mass production, long-term technical support and spare parts supply available
Built-in rich diagnosis functions, convenient for rapid fault location and on-site maintenance
Get a Quote