Honeywell 05701-A-0511 Single Channel Control Card
Description
Model Number Explanation
05701: System 57 / 5701 series (Sieger gas detection system)
A: Standard card assembly
0511: Single‑channel control card (basic display, no Modbus)
Technical Specifications
Channel: 1 × gas detector input (4–20 mA; catalytic bead compatible)
Display: LCD (4‑character numeric + bar graph; no advanced icons)
Front Panel LEDs: Power, Alarm 1 (A1), Alarm 2 (A2), Fault, Inhibit
Pushbuttons: Alarm reset / card select
Relay Outputs: 3 × SPCO (Form C): A1, A2, Fault
Contact Rating: 5 A @ 250 VAC / 30 VDC (resistive)
Analog Output: 1 × 4–20 mA (retransmit gas concentration)
Communication: None (no Modbus RTU; no digital comms)
Power Supply: 18–32 VDC (nominal 24 VDC, backplane‑fed)
Power Consumption: 3.25 W (4–20 mA input); 3.75 W (catalytic bead)
Alarm Setpoint Resolution: 1% FSD
Operating Temperature: −20°C to +60°C
Form Factor: 3U × 1” wide rack‑mount card (19” subrack)
Dimensions: 110 × 53 × 30 mm (H×W×D)
Weight: ~0.18 kg
Certifications: CE, TUV, UL 508, CSA
Key Features
Single‑channel monitoring: Dedicated to one gas detector (H₂S, LEL, CO, etc.)
Basic local HMI: Simplified LCD + LEDs for concentration, alarm, and fault status
Three alarm relays: Independent A1 (low), A2 (high), and fault outputs
4–20 mA retransmit: Analog output for connection to DCS/PLC
Hot‑swap capable: Insert/remove without powering down the rack
Cost‑optimized: No Modbus, minimal display—for standalone, non‑networked points
Applications
System Role: Basic single‑channel controller for System 57 gas detection racks
Industries: Oil & gas, petrochemical, power, water treatment, pharmaceuticals
Use Cases:
Standalone gas monitoring (no remote communication required)
Local alarm annunciation with beacon/horn
Small or remote monitoring points needing only local display/control
Cost‑sensitive projects without DCS/PLC integration
Compatibility & Replacement
System Compatibility: Honeywell System 57 (5701 series 19” subracks)
Field Devices: 4–20 mA gas detectors; catalytic bead sensors (with option)
Replacement Type: Direct drop‑in replacement
Legacy Status: Obsolete (EOL); available as refurbished/used stock
Quick Comparison (0511 vs 0351 vs 0361)
0511: Single‑channel, basic LCD + no Modbus, 3 relays, 4–20 mA out
0351: Single‑channel, full LCD + no Modbus, 3 relays, 4–20 mA out
0361: Engineering + single‑channel, full LCD + Modbus RTU, 3 relays, 4–20 mA out
Get a Quote