Honeywell 05701-A-0361 Engineering Control Card
Description
Model Number Explanation
05701: System 57 / 5701 series (Sieger gas detection system)
A: Standard card assembly
0361: Engineering / single‑channel control card (display + comms + I/O)
Technical Specifications
Channel: 1 × gas detector input (4–20 mA; optional catalytic bead)
Display: LCD (with bar graph, numeric readout, status icons)
Front Panel LEDs: Power, Alarm 1, Alarm 2, Fault, Inhibit
Relay Outputs: 3 × SPCO (Form C): A1, A2, Fault
Contact Rating: 5 A @ 250 VAC / 30 VDC (resistive)
Analog Output: 1 × 4–20 mA (retransmit gas concentration)
Communication: Modbus RTU (RS‑485) for remote monitoring/config
Power Supply: 18–32 VDC (nominal 24 VDC, backplane‑fed)
Power Consumption: ~1.5 W (typical)
Operating Temperature: −20°C to +60°C
Form Factor: 3U × 1” wide rack‑mount card (19” subrack)
Dimensions: 132 × 25 × 170 mm (H×W×D)
Weight: ~0.152 kg
Certifications: CE, TUV, UL 508, CSA
Key Features
Dual‑mode operation: Engineering mode for system-wide configuration; control mode for single‑channel gas monitoring.
Integrated I/O & display: Local readout and direct control via on‑card LCD/LEDs and pushbuttons.
Modbus RTU communication: Remote access to readings, status, and configuration; easy DCS/PLC integration.
Three alarm relays: Independent A1 (low), A2 (high), and fault outputs for safety annunciation.
Hot‑swap capable: Insert/remove without powering down the rack.
Calibration & diagnostics: On‑board tools for detector calibration, fault logging, and firmware upgrades.
Applications
System Role: Engineering tool + single‑channel gas detection controller for System 57 racks.
Industries: Oil & gas, petrochemical, power, pharmaceuticals, hazardous safety.
Use Cases:
System commissioning, calibration, and maintenance.
Standalone monitoring of H₂S, LEL, CO, etc.
Local alarm annunciation + remote Modbus RTU telemetry.
Small or remote monitoring points requiring display & control.
Compatibility & Replacement
System Compatibility: Honeywell System 57 (5701 series 19” subracks).
Field Devices: 4–20 mA gas detectors (catalytic bead compatible with option).
Replacement Type: Direct drop‑in replacement.
Legacy Status: Obsolete (EOL); available as new surplus or refurbished.
Quick Comparison (0351 vs 0361)
0351: Single‑channel control card (display + 3 relays; no Modbus; primarily for control)
0361: Engineering + single‑channel control (display + 3 relays + Modbus RTU; adds system‑wide configuration/maintenance functions)
Get a Quote