Honeywell 80363972-150 (MC-PDIY22) Digital Input Module
Description
Model Number Explanation
80363972-150
8036: Honeywell DCS I/O series
3972: Digital Input (DI) function
150: Standard revision, non-conformal coated
MC-PDIY22: Module code (M=Module, C=Control, PD=Digital Input, IY=Input Type, 22=32-channel standard)
Technical Specifications
Channels: 32 isolated digital inputs
Input Voltage: 24 VDC ±10%
Input Logic:
ON: 18–30 VDC
OFF: 0–5 VDC
Input Current: ~10 mA per channel @ 24 VDC
Response Time: ≤10 ms
Backplane: 5 VDC, 1.2 A max
Dimensions (mm): 319 × 279 × 29
Weight: Approx. 0.58 kg
Operating Temperature: -20°C to +70°C
Isolation: 1500 V AC (field-to-backplane)
Coating: Non-conformal coated
Certifications: CE, UL, RoHS
Interfaces & Configuration
Backplane: TDC3000 HPM / Experion PKS C300 I/O rack, hot-swappable
Front Panel: PWR/RUN/FAULT LEDs, diagnostic port
Terminals: 32-channel screw terminals, 24 VDC field side
Software: Control Builder, TDC3000 tools; channel enable/disable, debounce time
Key Features
32 High-Speed Inputs: Suitable for large I/O count systems
24 VDC Field Interface: Matches standard industrial sensors/switches
Channel-to-Channel Isolation: Reduces crosstalk and improves noise immunity
Debounce Filtering: Software-configurable for contact bounce suppression
Fault Detection: Open/short circuit indication, module diagnostics
UCN Communication: Seamless integration with Honeywell DCS networks
Applications
Systems: Honeywell TDC3000 (TPS), Experion PKS C300/C200 DCS
Typical Uses:
Petrochemical: Valve limit switches, pressure/level alarms
Power: Boiler interlocks, pump status, safety system inputs
Water Treatment: Flow switch, level switch, fault contacts
Manufacturing: Machine status, safety gates, pushbuttons
Companion Parts: FTA terminal board, 24 VDC power supply, backplane
Compatibility & Replacement
Related Models:
80363972-176: Conformal coated version (same form/fit/function)
Replacement: 80363972-150 is drop-in compatible with 80363972-176 (coating difference only).
Get a Quote