Honeywell 51405045-175 (CC-PAIM01) Low-Level Analog Input Module
Description
Model Number Explanation
51405045-175
51405: Honeywell Experion PKS Series C I/O Hardware
045: Low-Level Analog Multiplexer (TC/RTD)
175: Standard revision, industrial-grade, conformal coating
Technical Specifications
Input Types: Thermocouple (J/K/T/E/R/S/B/N), RTD (PT100/PT1000, Ni120, Cu10)
Channel Capacity: 16 channels (per module); expandable to 64 points via multiplexing
Resolution: 16-bit (0.01°C for RTD, 0.1°C for TC)
Measurement Ranges:
TC: -200°C ~ +1800°C (type-dependent)
RTD: -200°C ~ +850°C
Accuracy: ±0.05% FS @ 25°C (RTD); ±0.1% FS (TC)
Cold Junction Compensation (CJC): On-board, ±0.1°C accuracy
Diagnostics: Open/short-circuit detection, OTD (Open Thermocouple Detection)
Power: 24 V DC ±10%, 1.0 A (max)
Dimensions (mm): 178 × 79.4 × 127 (standard Series C I/O card)
Weight: Approx. 0.65 kg
Operating Temperature: -40°C ~ +85°C (extended industrial range)
Isolation: 1500 V AC (field-to-backplane)
Compatibility: Experion PKS C300/C200 controllers, PMIO bus, Control Builder Plus
Interfaces & Configuration
Backplane: PMIO bus slot in Series C I/O chassis, hot-swappable
Front Panel: Status LEDs (PWR, RUN, FAULT, CHANNEL), diagnostic port
Terminals: 16-channel screw terminals (2/3/4-wire RTD, TC connections)
Configuration: Control Builder Plus software; sensor type selection, scaling, CJC setup, fault thresholds
Key Features
Low-Level Signal Handling: Optimized for weak TC/RTD signals with high noise immunity
High-Density Multiplexing: 16 channels per module, reducing rack space and wiring
Multi-Sensor Compatibility: Supports all common TC and RTD types for flexible temperature monitoring
On-Board CJC: Accurate cold junction compensation for thermocouple measurements
Comprehensive Diagnostics: Real-time sensor fault detection and alarm reporting
Extended Temperature Range: Suitable for harsh industrial environments (-40°C to +85°C)
Seamless Integration: Works with Experion PKS C300 controllers and PMIO I/O infrastructure
Applications
Systems: Honeywell Experion PKS C300/C200 DCS (Series C I/O racks)
Typical Setup: 51405045-175 + C300 controller + TC/RTD sensors + FTA terminal board
Industries: Oil & gas, petrochemical, power generation, pulp & paper, pharmaceuticals, metal processing
Use Case: Reactor temperature monitoring, furnace/boiler control, pipeline heat tracing, environmental monitoring, turbine temperature sensing
Compatibility & Replacement
Related Modules: CC-PAIH01 (HART analog input), CC-PAIM02 (high-density 32-channel version)
Replacement Model:
51405045-175 (CC-PAIM01): Standard 16-channel low-level analog input module
Get a Quote