Honeywell 51404223-001 (RTD Input Module)
Description
Model Number Explanation
51404223-001
5140: Honeywell DCS Core Hardware Series
42: I/O Subsystem & Interface Control
23: RTD Temperature Acquisition Card
001: Standard revision, 16-channel, industrial-grade
Technical Specifications
Input Type: RTD (PT100, PT1000, Ni120, Cu10)
Channel Capacity: 16 channels (isolated per channel)
Resolution: 16-bit (0.01°C precision)
Measurement Range: -200°C ~ +850°C (configurable)
Accuracy: ±0.05% FS @ 25°C
Power: 24 V DC ±10%, 0.8 A (max)
Dimensions (mm): 365 × 128 × 20 (standard TDC3000 full-height card)
Weight: Approx. 0.5 kg
Operating Temperature: -25°C ~ +70°C
Isolation: 1500 V AC (channel-to-backplane)
Compatibility: TDC3000 R500–R610, TPS R100–R120 (HPM/UCN racks)
Interfaces & Configuration
Backplane: Dedicated slot in HPM/UCN chassis, hot-swappable
Front Panel: Status LEDs (PWR, RUN, FAULT), diagnostic port
Terminals: 16-channel screw terminals (3-wire/4-wire RTD connection)
Configuration: TPS System Software; channel scaling, sensor type selection, fault thresholds
Key Features
High-Precision Temperature Measurement: 16-bit resolution for accurate process temperature monitoring
Multi-Sensor Support: Compatible with PT100/PT1000 and other common RTD types
Channel Isolation: Galvanic isolation between channels to eliminate crosstalk
On-Board Diagnostics: Open/short-circuit detection, sensor fault alarm reporting
Seamless Integration: Works with HPM controllers, UCN network, and Experion PKS
Industrial Durability: Withstands harsh environments, vibration, and electrical noise
Applications
Systems: Honeywell TDC3000, TPS (HPM/UCN I/O Racks)
Typical Setup: 51404223-002 + HPM controller + RTD sensors + FTA terminal board
Industries: Oil & gas, petrochemical, power generation, pulp & paper, pharmaceuticals
Use Case: Reactor temperature monitoring, furnace control, pipeline heat tracing, environmental monitoring
Compatibility & Replacement
Related Modules: 51404223-002 (extended temperature), MC-TAMR04 (high-density RTD module)
Replacement Model:
51404223-001: Standard 16-channel RTD input module
51404223-002: Extended temperature (-40°C ~ +85°C) version
Get a Quote