Honeywell 51402083-100 (WSI2 Graphics Processor Module)
Description
Model Explanation
51402083-100
5140: Honeywell DCS Core Hardware Series
20: LCN Workstation Interface Sub-series
83: WSI2 Second Generation Graphics Processor
100: Hardware Version (64MHz, Standard Version without Graphics Acceleration)
Alias: WSI2-64 (64MHz Main Frequency) Technical Specifications
Processor: Dedicated graphics processor, 64 MHz clock frequency
Memory: 4MB RAM (for graphics cache and data buffering)
Communication interface: LCN redundant A/B network, operation station bus interface
Supported operation stations: GUS (Global User Station), US (Universal Station)
Maximum number of screens: Single card supports 8 concurrent operation station graphics
Refresh rate: Standard screen 1–2 seconds / frame
Power supply: 5 VDC (power supply from the back panel), approximately 600 mA
Operating temperature: 0°C ~ +60°C
Size (mm): 216 × 160 × 30
Weight: Approximately 0.5 kg
Firmware: Compatible with TDC3000 R500~R610, TPS R100~R120
Interfaces and configurations
Installation: Standard LCN rack slots (support hot swapping)
Panel indicators: PWR, LCN A/B, RUN, FAULT, STBY, etc. LEDs
Configuration: Set LCN address, number of operation stations, redundancy mode through TPS software
Redundancy: Supports 1:1 hot backup, fault switching < 200 ms
Core functions
Graphics rendering: Real-time generation and refreshing of operation station flowcharts, trend charts, alarm screens
LCN communication: Exchange control instructions, process data, alarm information with LCN network
Operation station management: Multiple operation station access, permission control, screen switching scheduling
Historical data processing: Historical trends, report data caching and forwarding
System diagnosis: Hardware self-check, LCN communication failure, operation station offline alarm Application scenario
Adaptation system: Honeywell TDC3000, TPS (LCN architecture)
Industry: Petrochemicals, thermal power, metallurgy, papermaking, pharmaceuticals, etc. process industries
Typical configuration: LCN rack + 51402083-100 (WSI2) + GUS/US operation station