Honeywell 51401642-150 (High-performance I/O Link Card)
June 01, 2026

Honeywell 51401642-150 (High-performance I/O Link Card)

Product Introduction 51401642-150 is a high-performance I/O link card in the Honeywell Experion PKS/TPS/TDC3000 system, used for high-speed, redundant communication between the C300 controller and the remote I/O rack, and is a key data channel between the control layer and the field I/O.

Description

Model Explanation

5140: Honeywell DCS Hardware Series

16: UCN Control Network Sub-series

42: High Performance I/O Link (High Performance I/O Link)

150: Hardware Version (Standard Configuration Version, with Redundant HIO Interface) Technical Specifications

Communication Protocol: HIO (Honeywell I/O Link), based on RS-485

Number of Links: 2 × redundant HIO ports (A/B network)

Transmission Rate: Up to 2 Mbps

Communication Distance: Single segment maximum 1200 m (repeaterable)

Processor: 32-bit RISC

Power Supply: 5 VDC (power supply from the backplane), approximately 400 mA

Operating Temperature: 0°C ~ +60°C (industrial grade)

Size (mm): Approximately 30 × 250 × 200

Weight: Approximately 0.8 kg

Certifications: CE, UL, CSA, SIL2

Interfaces and Configuration

Installation: Slot of C300 controller chassis, supports hot swapping

Panel Indicators: PWR, COM A/B, ACT, FAULT, REDY, etc. LED

Configuration: Set link address, baud rate, redundancy mode through Experion PKS/TPS software

Redundancy: Supports 1:1 link redundancy, fault switching < 50 ms

Core Functions

High-speed I/O Data Exchange: C300 reads and writes with remote I/O (such as FTA, I/O subrack) in real time

Link Redundancy Management: Both HIO links work simultaneously, automatic seamless switching occurs when a single link fails

I/O Subrack Expansion: One card can carry multiple I/O subracks, supports distributed I/O architecture

Diagnosis and Alarm: Report faults such as link interruption, CRC error, node offline, etc. to the system

Time Synchronization: Support full network time synchronization to ensure consistent SOE event timing Application scenario

System: Honeywell Experion PKS, TPS, TDC3000 (C300 controller platform)

Industry: Petrochemicals, power, metallurgy, papermaking, pharmaceuticals, etc. (process industries)

Typical configuration: C300 controller + 51401642‑150 + remote I/O subrack (such as 51401643‑150)