Product Introduction 51401583-100 is the core communication interface board of Honeywell TDC 3000/TPS system. It is used to connect LCN (Local Control Network) and Data Hiway (Data Highway), enabling high-speed and reliable data transmission and management between system nodes and field devices. It is a key component of the DCS system network architecture.

Description

Model Explanation

51401583-100: Standard Model

51401583: TDC 3000 Enhanced Process Network Interface (EPNI) Series

100: Hardware Version (Standard Edition)

Module Type: Network Communication Interface Card (EPNI)

Applicable Systems: Honeywell TDC 3000, TPS, Experion PKS (LCN Network) Technical Specifications

Communication protocol: LCN protocol, Data Hiway protocol

Data transmission rate: LCN 5 Mbps; Data Hiway 250 Kbps

Number of network nodes: Supports up to 64 LCN nodes

Power supply: 24 VDC (±10%), approximately 300 mA

Operating temperature: 0°C ~ +60°C

Storage temperature: -40°C ~ +85°C

Weight: Approximately 0.5 kg

Certifications: CE, UL, CSA, RoHS

Interfaces and Configuration

Backplane interface: 96-pin finger contacts (compatible with TDC 3000 I/O backplane)

Network interfaces:

LCN interface: Coaxial cable (BNC connector)

Data Highway interface: Twisted pair (DB-25 connector)

Status indicators: LEDs (power, operation, LCN communication, Data Highway communication, fault)

Configuration method: DIP switches (network address, communication mode, baud rate)

Core functions

Protocol conversion: Achieve mutual conversion between LCN and Data Highway protocols,打通 system-level communication

Data routing: Efficiently forward control instructions, process data and status information

Network management: Node monitoring, fault diagnosis, communication redundancy switching

Signal isolation: Electrical isolation, suppressing ground loops and industrial interference

System expansion: Supports multi-node, multi-device access, enhancing system scale and compatibility Application scenario

System: Honeywell TDC 3000, TPS, Experion PKS

Industry: Petrochemicals, Electricity, Metallurgy, Papermaking, Pharmaceuticals

Application: DCS system network setup, LCN communication with field controllers/PLCs

Installation: TDC 3000 standard I/O rack (5 slots / 15 slot backplane, such as 51401381-100)

Compatible modules

Backplane: 51401381-100 (5 slots), 51401547-100 (15 slots)

Processor: 51400978-100, 51401570-100 (PMM)

Communication card: 51401551-300/301 (LCN interface)

I/O module: 51401573-100 (TC MUX), 51401503-100 (AI), etc.