Product Introduction 51401573-150 is a field terminal assembly board (FTA) that is used in conjunction with 51401573-100 (LLAI TC MUX motherboard) in the Honeywell TDC 3000/TPS system. It is responsible for the connection of field thermocouple signals, terminal conversion, signal protection and filtering, and serves as the interface board card for connecting field sensors to the DCS input card.

Description

Model Explanation

51401573-150: Standard FTA model

51401573: TDC 3000 low-level analog input / thermocouple multiplexing series

150: FTA version (corresponding to the dedicated terminal board of the mainboard 51401573-100)

Associated mainboard: 51401573-100 (LLAI TC MUX mainboard, 16 thermocouple inputs)

Module type: Thermocouple (TC) input terminal board (FTA)

Applicable systems: Honeywell TDC 3000, TPS, Experion PKS (LCN network) Technical Specifications

Input Channel: 16 differential channels (corresponding one-to-one with the motherboard 51401573-100)

Signal Type: J, K, T, E, R, S, B type thermocouples (mV level low voltage)

Terminal Specification: Screw type, compatible with 14–22 AWG cables

Isolation Voltage: 1500 VAC (channel - motherboard)

Protection Functions: Overvoltage, Overcurrent, Reverse Polarity Protection

Filtering: RC low-pass filtering (suppresses high-frequency interference)

Power Supply: Powered by the motherboard 51401573-100 (no external power supply required)

Operating Temperature: 0°C ~ +60°C

Storage Temperature: -40°C ~ +85°C

Weight: Approximately 0.18 kg

Certifications: CE, UL, CSA, RoHS

Interface and Configuration

Field Side: 16 differential input terminals for thermocouples (plus/minus)

Backplane Side: Special connector for connection with the 51401573-100 motherboard

Status Indication: No onboard LED (status indicated by motherboard indicator lights)

Configuration Method: No DIP switches (channel type / parameters configured by motherboard software)

Installation: Stack-mounted with the motherboard 51401573-100, fixed in the I/O rack

Core Functions

Signal Conversion: Connects 16 on-site thermocouple signals to the motherboard

Electrical Isolation: Isolates the field from the system side, suppressing ground loop interference

Signal Protection: Prevents damage to the motherboard's precision circuits due to overvoltage / overcurrent

Filtering and Noise Reduction: Filters out high-frequency noise from industrial sites, improving measurement accuracy

Cold Junction Compensation Assistance: Provides a stable reference point, cooperating with the motherboard's cold junction compensation Application scenario

System: Honeywell TDC 3000, TPS, Experion PKS

Industry: Petrochemicals, power, metallurgy, heat treatment, pharmaceuticals, glass

Application: Monitoring of multiple points for heating furnaces, reactors, boilers, steam turbines, etc.

Installation: TDC 3000 standard I/O rack (5 slots / 15 slots backplane, such as 51401381-100)