Honeywell 51401491-150 (MC‑TAMT02 Low Level Analog Input Multiplexer)
Description
Model Definition
51401491-150: Honeywell standard part number
51401491: Series code for low‑level analog multiplexer modules
150: Hardware revision G/E, upgraded firmware, conformal coated, industrial temp range
Module Type: Low‑Level Analog Input Multiplexer (LLMux)
Applicable System: Honeywell TDC 3000, TPS (LCN/UCN nodes), Experion PKS
Alias: MC‑TAMT02 (vs. MU‑TAMT02 for 51401491-100)
Technical Specifications
Input Channels: 16 differential low‑level analog inputs (thermocouple, mV)
Signal Types: Thermocouple (J, K, T, E, N, R, S, B), ±100 mV millivolt
Resolution: 16‑bit ADC, accuracy ±0.02% FS
Filtering: 2 Hz programmable low‑pass filter, built‑in noise rejection
Isolation: 2500 VAC channel‑to‑backplane galvanic isolation
Power Supply: 24 VDC (±10%), ≤200 mA
Operating Temperature: ‑20°C to +70°C (wider than 51401491-100)
Storage Temperature: ‑40°C to +85°C
Humidity: 5%–95% RH (non‑condensing)
Coating: Conformal coated for corrosion/moisture resistance
Dimensions: 307 mm × 100 mm × 45 mm (Size B)
Weight: Approx. 1.2 kg
Certifications: CE, UL, CSA, RoHS, FM compliant
Interfaces & Configuration
Field Interface: Screw terminals for thermocouple/mV signal wiring
Backplane Interface: Gold‑finger connector for system power and communication
Configuration: Onboard DIP switches for channel enable, filter frequency, TC type, and fault response
Redundancy: Supports 1:1 hot standby with auto failover
Diagnostics: LED indicators for power, channel status, fault, and communication; onboard self‑diagnostics
Key Functions
16‑Channel Low‑Level Signal Multiplexing: Gathers weak thermocouple/mV signals and routes to controller.
Precision Signal Conditioning: Amplifies, filters, and isolates low‑level signals for accuracy and noise immunity.
Multi‑TC Support: Handles 8 thermocouple types with cold‑junction compensation (CJC).
High‑Speed Conversion: 16‑bit ADC converts analog to digital for reliable backplane transmission.
Enhanced Reliability: Conformal coating and wider temp range for harsh environments.
Fault Detection: Monitors open/short circuits and out‑of‑range signals; reports to DCS.
Application Scenarios
Systems: Honeywell TDC 3000, TPS, Experion PKS
Industries: Petrochemical, power generation, metallurgy, pharmaceutical, pulp & paper
Applications: Temperature monitoring, thermocouple data acquisition, low‑level mV logging, process loop control
Mounting: Standard 19‑inch I/O cabinet, Honeywell TDC 3000 I/O racks
Differences from 51401491-100
Part Number: 51401491-150 (MC‑TAMT02) vs. 51401491-100 (MU‑TAMT02)
Temperature Range: ‑20°C to +70°C vs. 0°C to +60°C
Coating: Conformal coated vs. non‑coated
Firmware: Upgraded, more robust for industrial use
Reliability: Higher tolerance to moisture, dust, and temperature swings
Get a Quote