Honeywell 51401491-100 (MU-TAMT02 Low Level Analog Input Multiplexer)
Description
Model Definition
51401491-100: Honeywell standard part number
51401491: Series code for low‑level analog multiplexer modules
100: Standard version, hardware revision C/E, firmware revision E
Module Type: Low‑Level Analog Input Multiplexer (LLMux)
Applicable System: Honeywell TDC 3000, TPS (LCN & UCN nodes)
Alias: Thermocouple Mux Filter, MU‑TAMT02, Low‑Level Analog Mux FTA
Technical Specifications
Input Channels: 16 differential low‑level analog inputs (thermocouple, mV)
Signal Type: Thermocouple (J, K, T, E, R, S, B), millivolt (±100 mV)
Resolution: 16‑bit ADC, accuracy ±0.02% of full scale
Filtering: Built‑in low‑pass filter (2 Hz programmable) for noise rejection
Isolation: 2500 VAC channel‑to‑backplane galvanic isolation
Power Supply: 24 VDC (±10%), power consumption ≤ 200 mA
Operating Temperature: 0°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH (non‑condensing)
Dimension: 120 mm × 60 mm × 45 mm
Weight: Approx. 1.14 kg
Certifications: CE, UL, CSA, FM, RoHS compliant
Interfaces & Configuration
Field Interface: Screw terminals for thermocouple/mV signal connection
Backplane Interface: Gold‑finger connector for system power and communication
Configuration: Onboard DIP switches for channel enable, filter frequency, thermocouple type
Redundancy: Supports 1:1 hot standby with automatic failover
Diagnostics: LED indicators for power, channel status, fault, and communication
Key Functions
Low‑Level Signal Multiplexing: Gathers 16 channels of weak analog signals (thermocouple/mV) and routes them to the controller.
Precision Signal Conditioning: Amplifies, filters, and isolates low‑level signals to improve accuracy and noise immunity.
Thermocouple Input Handling: Supports multiple thermocouple types with cold‑junction compensation (CJC).
High‑Speed Data Conversion: Converts analog signals to 16‑bit digital data for reliable transmission over the backplane.
Fault Detection & Reporting: Monitors for open circuits, short circuits, and out‑of‑range signals; reports to DCS.
Application Scenarios
Systems: Honeywell TDC 3000, TPS, Experion PKS
Industries: Petrochemical, power generation, metallurgy, pharmaceutical, pulp & paper
Applications: Temperature monitoring, thermocouple data acquisition, low‑level mV signal logging, process loop control
Mounting: Standard 19‑inch I/O cabinet, compatible with Honeywell TDC 3000 I/O racks
Get a Quote