Honeywell 51401291-100 (LLCN Control Board)
June 01, 2026

Honeywell 51401291-100 (LLCN Control Board)

Product Introduction 51401291-100 is the LLCN control board of Honeywell TDC 3000 DCS, installed in the LCN network node cabinet. It is responsible for the underlying data link control, signal transmission and reception, protocol conversion, and physical layer management of the LCN network. It is the key interface card for LCN network communication.

Description

Model Explanation

51401291-100: Honeywell part number (written as 51401291100)

51401291 = LLCN Control Board Series

100 = Standard version, Hardware Rev A, Basic Firmware

Component Type: LLCN Control Board (Low-Level LCN Communication Control Card)

Compatible System: TDC 3000 (LCN Network Node, HPM/UCN Controller)

Alias: Low-Level LCN Board, LCN Physical Interface Card Technical Specifications

Processor: Specialized communication processor, 16-bit, with a main frequency of 16 MHz

Memory: 512KB RAM (communication cache), 256KB ROM (firmware)

Communication rate: LCN bus 5Mbps (compatible with standard LCN protocol)

Interface: LCN coaxial interface (BNC), LCN network cable connection

Power supply: 5VDC/±12VDC (backplane), power consumption ≤ 18W

Operating temperature: 0°C ~ +60°C

Storage temperature: -40°C ~ +85°C

Humidity: 5%~95% RH (no condensation)

Size: Standard 19-inch card (6U)

Weight: Approximately 1.2kg

Certifications: CE, UL, CSA, FM

Interface and Configuration

LCN Interface: BNC coaxial interface, connects LCN network cable

Backplane Interface: Gold finger, connects LCN node backplane

Configuration Method: Built-in DIP switches (LCN address, termination resistor, communication mode)

Redundancy: Supports 1:1 hot redundancy, automatic fault switching

Compatibility: Full version LCN network of TDC 3000, compatible with HPK2-2/3 processor card Core function

LCN Physical Layer Control: LCN network signal modulation/demodulation, transmission/reception control, level conversion, ensuring the stability of the network physical link.

Data Link Management: LCN frame encapsulation/deserialization, error checking, retransmission control, communication scheduling, achieving reliable data transmission.

Protocol Conversion: LCN protocol conversion with backplane bus protocol, connecting LCN network and internal processor of the node.

Network Diagnosis and Monitoring: LCN network status monitoring, fault location, alarm reporting, supporting network maintenance.

Redundancy Switching Control: Automatically detects the failure of the main card under redundant configuration, seamlessly switches to the backup card without data loss. Applicable scenarios

System: Honeywell TDC 3000, TPS (LCN network node, HPM/UCN controller)

Equipment: LCN node cabinet, HPK2-2/3 processor card, LCN network cable

Industry: Petrochemicals, thermal power, metallurgy, oil and gas, pharmaceuticals, papermaking

Application: LCN network communication, process data transmission, system network redundancy, network fault diagnosis