Honeywell 51401183-100 (MU-TAIL01, UCN Low-Level Analog Input Module)
Description
Model Explanation
51401183-100: Honeywell part number (written as 51401183100)
51401183 = LLAI (Low Level Analog Input) low-level analog input module series
100 = Standard version, Rev C hardware, Rev B firmware, with signal conditioning
Component Type: LLAI PWA (Printed Circuit Board Assembly) + MU-TAIL01 FTA terminal board
Compatible Systems: TDC 3000, TPS, Experion PKS (UCN network)
Alternative Model: No direct alternative, UCN-specific low-level signal acquisition card Technical Specifications
Processor: Specialized signal conditioning processor, with a main frequency of 20 MHz
Number of channels: 8 differential low-level analog inputs
Input signal types: Thermocouples (K, S, R, B, E, J, T), RTD (PT100, PT1000), ±50 mV, ±100 mV, ±500 mV
Resolution: 16 bits (0.0015% full scale)
Accuracy: ±0.02% F.S. (25°C), ±0.05% F.S. (full temperature range)
Sampling rate: 10 Hz/channel, synchronous sampling
Isolation: 1500 VAC between channels, 2500 VAC between channel and backplane
Backplane interface: UCN dedicated bus, rate 5 Mbps
Power supply: 24 VDC (backplane, ±10%), power consumption ≤ 18 W
Operating temperature: 0°C ~ +60°C
Storage temperature: -40°C ~ +85°C
Humidity: 5% ~ 95% RH (no condensation)
Size: Standard 19-inch card (3U), UCN I/O slot
Weight: Approximately 1.2 kg (including FTA)
Certifications: CE, UL, CSA, FM, TÜV
Interface and Configuration
External interfaces: FTA terminal board (MU-TAIL01), screw wiring, supports direct connection of thermocouples/RTD
Backplane interface: UCN cabinet gold fingers, dedicated high-speed data bus
Configuration method: System software configuration (signal type, range, filtering, cold junction compensation) + onboard jumpers (address, terminal resistor)
Redundancy: Supports 1:1 hot redundancy, automatic fault switching, no data loss
Compatibility: Compatible with TDC 3000 UCN full version, compatible with Experion PKS system Core function
High-precision acquisition of low-level signals: Compatible with thermocouples, RTDs, and millivolt sensors, with amplification, filtering, and cold junction compensation for weak signals, ensuring accurate measurement of industrial site temperatures and weak parameters.
Compatibility with multiple signal types: Supports mainstream thermocouples, RTDs, and millivolt voltage inputs, with a single card supporting multiple sensors, reducing the variety of spare parts and costs.
Signal isolation and anti-interference: High-voltage isolation between channels, built-in digital filtering and signal shielding, suppressing electromagnetic interference in industrial sites, ensuring stable data in harsh environments.
UCN network data interaction: The collected data is transmitted to the controller via the UCN bus, supporting real-time monitoring, trend recording, and alarm triggering, providing reliable data for process control.
Self-diagnosis and alarm for faults: Built-in channel short circuit, open circuit, and over-range diagnosis, real-time reporting of fault information, facilitating rapid location and maintenance. Applicable scenarios
System: Honeywell TDC 3000, TPS, Experion PKS (UCN network)
Equipment: UCN cabinet, FTA terminal board, thermocouple, RTD, millivolt-level sensor
Industry: Petrochemicals, thermal power, nuclear power, metallurgy, cement, pharmaceuticals, glass
Application: Industrial furnace temperature monitoring, reactor temperature control, high-precision temperature inspection, weak signal acquisition, environmental monitoring