Honeywell 51400667-100 (LCN Interface Card)
Description
Model Explanation
51400667-100: Honeywell part number (without delimiter, i.e. 51400667100)
51400667 = LCN interface card series
100 = Standard hardware version, compatible with Rev A/B/C
Component Type: LCN Interface Board (LCN interface board)
Compatible Processors: Non-integrated processor nodes such as HPK2-2, HPK2-3, HMPU, etc. Technical Specifications
Network Protocol: LCN (Local Control Network)
Transmission Rate: 5 Mbps (standard rate of LCN)
Node Capacity: Single card supports 1 LCN node connection
Power Supply: 5 VDC (backplane power supply, ±5%)
Power Consumption: ≤ 15 W
Operating Temperature: 0°C ~ +60°C (environment of the cabinet)
Storage Temperature: -40°C ~ +85°C
Humidity: 5%~95% RH (no condensation)
Size: Standard 19-inch card (3U height)
Weight: 0.65 kg
Certifications: CE, UL, CSA
Interfaces and Configuration
Network Interface: LCN coaxial cable interface (BNC connector, 75Ω impedance)
Backplane Interface: Standard TDC 3000 cabinet slot (compatible with 51400665-100 backplane)
Status Indicators: PWR (power), LCN ACT (network activity), FAULT (fault) LEDs
Installation Method: Hot-swappable (supports on-line replacement)
Compatibility: Directly replace the old LCN interface card, compatible with the entire series of TDC 3000 cabinets Core function
LCN Network Access: Provides LCN network interfaces for older processors such as HPK2/HMPU, enabling communication and interconnection between the controller and the TDC 3000 system, and completing data acquisition, command issuance, and status reporting.
Data Forwarding and Protocol Conversion: Performs data format conversion and protocol adaptation between the internal bus of the processor and the LCN network, ensuring seamless data interaction between nodes of different architectures.
Network Status Monitoring: Monitors the communication status of the LCN network, data transmission quality, and link failures in real time. When an anomaly occurs, it triggers system alarms to facilitate rapid identification of network issues.
Redundant Communication Support: Supports dual LCN network redundancy configuration. In the event of a single network failure, it automatically switches, with the switching time being less than 50 ms, ensuring uninterrupted communication of critical control nodes.
Compatibility with Old Systems: Specifically adapted for early non-integrated processor nodes, addressing communication compatibility issues in the mixed architecture of new and old systems, and supporting smooth upgrade and expansion of the old system. Applicable scenarios
System: Honeywell TDC 3000, TPS, Experion PKS (compatible with older nodes)
Processor nodes: Non-integrated processor cabinets such as HPK2-2, HPK2-3, HMPU, etc.
Industry: Petrochemicals, thermal power, nuclear power, metallurgy, cement, glass, pharmaceuticals
Application: Old system renovation, access to older processor networks, LCN network expansion, replacement of communication fault cards, mixed networking of new and old systems
Get a Quote