Honeywell 51309218‑175(MC‑TAMR03)
Description
Model Explanation
51309218‑175: Honeywell Material Number (51309218 = RTD-specific LLMUX series; 175 = High-density wide-temperature enhanced version)
MC-TAMR03: Module Model
MC = Module Card (Enhanced I/O Board)
TAMR = Thermocouple Analog Multiplexer RTD (Thermocouple Analog Multiplexer for RTD)
03 = Hardware Version (Rev.03, Wide-temperature High-density Version) Technical Specifications
Channel quantity: 16 differential inputs (only RTD, no TC/mV)
Signal type: PT100/PT1000 (3-wire / 4-wire configuration)
Measurement range: -200°C ~ +850°C
Resolution: 16 bits (high-precision ADC)
Accuracy: ±0.1°C (at 25°C)
Isolation strength: 1500 V RMS (channel - system isolation)
Input impedance: >100 kΩ (RTD-specific)
Cold junction compensation (CJR): None (pure RTD)
Power supply: 24 VDC (±10%), UCN backplane power supply
Operating temperature: -40°C ~ +75°C (wide temperature industrial grade)
Storage temperature: -40°C ~ +85°C
Humidity: 5% ~ 95% RH (no condensation)
Size: 220 × 150 × 30 mm
Weight: 0.78 kg
Certifications: CE, UL, CSA, RoHS
Interfaces and Communications
Field side: 16 gold-plated screw terminals (3/4-wire RTD-specific)
System side: High-density UCN flat cable (connected to LLMUX IOP)
Status indication: PWR (green), READY (green), FAULT (red) LEDs
Configuration: DCS software configuration for RTD type, wiring, range, filtering
Hot-swappable: Supported (on-line replacement without system interruption) Core function
16-channel pure RTD high-precision acquisition: 3/4 line compatibility, accuracy ±0.1°C, suppresses lead resistance error
Wide temperature range with high stability: -40°C to +75°C, suitable for low/ high-temperature industrial environments
Enhanced isolation for anti-interference: 1500 V RMS isolation, resistant to EMI/RFI and ground loop interference
Comprehensive fault diagnosis: RTD open circuit / short circuit, over-range, power failure detection
High-density space-saving: 16 channels per card, compact cabinet layout, lower cost Applicable scenarios
Industry: Petrochemicals, Electricity, Metallurgy, Pharmaceuticals, Energy Management
Applications: 16-channel RTD high-precision temperature monitoring, extreme environment (low/ high temperature) measurement points, pure temperature-intensive loop
Compatible systems: Experion PKS (C200/C300), TDC 3000, TPS (UCN LLMUX IOP companion)
Get a Quote