Honeywell 51309213‑125 (MC‑TAMT12) Low-Level Analog Input Multiplexer (Low-Level Analog Input Multiplexer / LLMUX FTA)
Description
Product Introduction
51309213‑125 (MC-TAMT12) is a 16-channel low-level analog input multiplexer (LLMUX FTA) for the Honeywell Experion PKS / TDC 3000 / TPS DCS system, specifically designed to collect low-level signals such as thermocouples (TC), resistance thermometers (RTD), and micro-voltage levels in millivolts. It isolates, amplifies, and multiplexes multiple weak signals before sending them to IOP cards, serving as the core I/O board for precise temperature and weak signal acquisition.
Model Interpretation
51309213‑125: Honeywell part number (51309213 = LLMUX series, 125 = Standard Version / 16 channels)
MC-TAMT12: Module model
MC = Module Card (Standard I/O board)
TAMT = Thermocouple Analog Multiplexer (Thermocouple Analog Multiplexer)
12 = Hardware version (Rev.12, Industrial Standard Version) Technical Specifications
Channel quantity: 16 differential inputs (configurable as 8 RTD or 16 TC/mV)
Signal type: Thermocouple (B/E/J/K/N/R/S/T types), Thermoresistor (PT100/PT1000), ±50mV/±100mV low-level voltage
Resolution: 16 bits (high-precision analog-to-digital conversion)
Isolation strength: 1500V RMS (channel - system isolation, anti-ground loop interference)
Input impedance: >10MΩ (mV signal), >100kΩ (RTD)
Cold junction compensation (CJR): On-board high-precision CJR, accuracy ±0.5°C
Power supply: 24VDC (±10%), powered by UCN backplane
Operating temperature: 0°C ~ +60°C (standard industrial grade)
Storage temperature: -40°C ~ +85°C
Humidity: 5% ~ 95% RH (no condensation)
Size: 220 × 150 × 30 mm
Weight: 0.75 kg
Certifications: CE, UL, CSA (industrial safety certification)
Interfaces and Communications
Field side: 16 gold-plated screw terminals (anti-oxidation, compatible with TC/RTD/mV signal wiring)
System side: High-density UCN flat cable (connected to LLMUX IOP card)
Status indicators: PWR (power), READY (ready), FAULT (fault) LED indicators
Configuration: Configure channel type, range, filtering parameters through DCS system software
Hot-swappable: Supported (online replacement does not affect system operation) Core function
Multi-channel low-level signal acquisition: 16 differential inputs, compatible with TC/RTD/mV signals, suitable for industrial precise temperature and weak pressure/flow signal acquisition
Signal isolation and anti-interference: 1500V RMS electrical isolation, suppressing industrial environment ground loops and electromagnetic interference, ensuring the measurement accuracy of weak signals
High-precision cold-end compensation: On-board CJR, automatically compensating for the temperature error of thermocouples at the cold end, with temperature measurement accuracy reaching ±0.5°C
Signal amplification and multiplexing: Amplifying mV-level weak signals to the range that can be recognized by IOP, 16-channel time-division multiplexing, reducing the number of system I/O points
Fault diagnosis and alarm: Open circuit / short circuit detection, over-range alarm, power failure monitoring, indicator lights intuitively indicating the fault status Applicable scenarios
Industry: Petrochemicals, power (boilers / steam turbines), metallurgy, pharmaceuticals, food processing
Applications: 16-channel thermocouple temperature monitoring, RTD high-precision temperature measurement, collection of tiny voltage signals (such as strain bridges, pressure sensors)
Compatible systems: Experion PKS (C200/C300), TDC 3000, TPS (UCN network LLMUX IOP companion)