Honeywell 51309154‑225(MU‑TDOR29)
Description
Model Explanation
51309154‑225: Honeywell Material Number
MU-TDOR29: Module Model
MU = Module Unit (FTA Series)
TDOR = Total Digital Output Relay (Relay Output)
29 = Hardware Version and Channel Configuration Variant (Compared to Version 28, optimized surge suppression and EMI protection) Technical Specifications
Channel: 16 independent relay outputs (each channel has 1 normally open + 1 normally closed, Form C)
Contact capacity:
AC: 120/240 VAC, 5 A (resistive)
DC: 24 VDC, 5 A (resistive)
Isolation: 1500 V RMS (between channels, between channel and bus, mechanical isolation)
Response time: ≤ 10 ms (mechanical relay)
Switching frequency: Maximum 10 Hz
Power supply: Backplane 24 VDC
Operating temperature: -20°C ~ +70°C
Hot-swappable: Supported
Fault detection: Open circuit / short circuit (system diagnosis)
Relay life: ≥ 150,000 times (resistive load)
Surge resistance: Enhanced TVS protection (20% improvement compared to version 28)
Interface and status
System side: High-density flat cable connects I/O modules
Field side: Removable heavy-duty screw terminals (facilitating wiring and maintenance)
Indicators: ON/OFF status lights for each channel, module OK/Fault fault lights
Configuration: DCS workstation software configuration, supports individual enabling / disabling of channels
Core functions
Mechanical relay true isolation: Contacts are completely isolated when disconnected, resistant to high voltage surges and ground loop interference, high safety
Common AC/DC industrial load compatibility: Compatible with AC 120/240V, DC 24V, suitable for common industrial loads, strong versatility
Medium power circuit control: Electromagnetic valves, contactors, small motors, alarm lights, conventional heaters
Long-life stable output: Optimized relay contact material, longer lifespan, suitable for long-term continuous operation
Online replacement (hot-swappable): Supports maintenance without downtime, ensuring production continuity
System-level precise diagnosis: Real-time detection of open circuit / short circuit faults, rapid problem location Applicable scenarios
Industry: Oil and gas, petrochemicals, power generation, metallurgy, water treatment, chemicals
Applications: Loads requiring electrical isolation, AC/DC mixed control, medium power circuits, non-high-frequency conditions
Compatibility: Experion PKS (C200/C300), TDC 3000, TPS
Get a Quote