ABB CP420-B (CP420B)compact, cost-effective HMI
May 30, 2026

ABB CP420-B (CP420B)compact, cost-effective HMI

ABB CP420-B (also written CP420B) is a compact, cost-effective HMI in the CP400 series, with a 4.7‑inch blue STN touchscreen for basic machine and process visualization/operation. Model Interpretation

Description

Product Introduction

ABB CP420-B (also written CP420B) is a compact, cost-effective HMI in the CP400 series, with a 4.7‑inch blue STN touchscreen for basic machine and process visualization/operation.

Model Interpretation

  • CP: Control Panel

  • 420: Model in CP400 line

  • B: Hardware variant (blue STN, no Ethernet)

  • Ordering code: 1SBP260182R1001

Technical Parameters

  • Display: 4.7‑inch STN, 16 blue levels, 240×128 pixels, resistive touch

  • Memory: 4 MB flash, 512 KB RAM

  • Power: 24 V DC ±10%, consumption <500 mA

  • Environment: Operating 0–50°C; storage −40–85°C

  • Protection: Front IP65, rear IP20

  • Dimensions: 170×103×45 mm; weight 0.47 kg

  • Clock: Built‑in lithium battery for RTC backup

Interface & Communication

  • Serial: RS232 + RS485 (supports Modbus RTU, ASCII)

  • USB: For project upload/download and data storage

  • No Ethernet port

  • Programming: CP400 Soft software

Core Functions

  • Real‑time data display and manual operation

  • Customizable graphical screens

  • Alarm handling, data logging, recipe management

  • Multi‑language support and user permissions

  • Offline simulation and online debugging

Application Scenarios

  • Machine tools, packaging machines, assembly lines

  • Water treatment, food & beverage, pharmaceutical

  • Building automation (HVAC, energy management)

  • Conveying equipment, small automated units

  • Plastics, textile, printing machinery

Operation & Maintenance

  • Panel‑mount in cabinet cutout; install sealing ring for IP65

  • Use shielded cables for communication; separate power/signal wires

  • Check power polarity and protection before power‑on

  • Design projects with CP400 Soft

  • Clean touchscreen with mild detergent; avoid corrosives

  • Periodically inspect cables/terminals; back up projects

  • Take anti‑static precautions; avoid strong vibration/direct sunlight


Get a Quote