ABB 5SGY-55L4500(5SHY55L4500)high-power asymmetric Integrated Gate-Commutated Thyristor (IGCT) module
Description
Product Introduction
Model Interpretation
5S: ABB high-power semiconductor product line
GY: Asymmetric IGCT with unidirectional switching
55: 5500 A class current rating
L: Low-loss optimized version
4500: 4500 V repetitive peak blocking voltage
This is a high-current, medium-frequency optimized base variant.
Technical Parameters
Repetitive peak blocking voltage (VDRM): 4500 V
Permanent DC voltage (VDC): 2800 V
Max continuous on-state current (ITGQM): 5000 A
Peak surge current (ITSM): 33 kA
Typical on-state voltage drop (VT0): 1.22 V
On-state resistance (rT): 0.28 mΩ
Max switching frequency: up to 1000 Hz (medium-frequency optimized)
Operating junction temperature: −40 °C to +125 °C
Storage temperature: −40 °C to +85 °C
Cooling: deionized water-cooled baseplate
AC insulation (main terminals): 12 kV
Mounting clamping force: 36–44 kN
Weight: approx. 4.2 kg
Interface and Communication Configuration
Integrated gate drive with fiber-optic control interface, offering high electromagnetic interference immunity
Main power terminals: large copper busbars for low-resistance, high-current connections
Water-cooled baseplate for efficient heat dissipation
Built-in temperature and current sensors for real-time status monitoring and fault diagnosis
Status feedback via fiber optics for system control and protection
Gate unit supply: AC square wave or DC input
Core Functions
Provides stable 4500 V / 5000 A high-power switching for medium-voltage conversion systems
Ultra-low conduction and switching losses enhance overall system energy efficiency
Snubberless fast turn-off capability simplifies peripheral circuit design
Rugged press-pack structure ensures long-term stable operation under harsh industrial conditions
Optimized for medium frequencies (<1 kHz), ideal for high-power dynamic applications
High cosmic radiation withstand rating for grid-critical installations
Application Scenarios
Medium-voltage variable frequency drives (e.g., ABB ACS6000 series)
Static Var Compensators (SVC) and STATCOM for grid power quality regulation
Wind turbine converters and high-power photovoltaic inverters
HVDC Light transmission systems
Heavy industries: power generation, metallurgy, mining, oil and gas
Operation and Maintenance Instructions
Mount the module on a water-cooled heat sink with a clamping force of 36–44 kN
Connect main terminals with professional high-current busbars; use dedicated fiber-optic cables for gate signals
Maintain the cooling system with qualified deionized water at stable flow and pressure
Conduct quarterly inspections of appearance, electrical connections, and cooling system performance
Before disassembly or replacement, fully de-energize the system and discharge residual voltage
Handle with anti-static protection to avoid electrostatic discharge damage
Get a Quote