ABB 1SBP260011R2002 (commercial model 07KR51‑R2002) compact, integrated basic controller
Description
Product Introduction
Model Interpretation
1SBP: ABB AC31/Procontic CS31 series controller prefix.
260011: Base model code for 07KR51 with 120/230 V AC power.
R2002: Updated hardware revision (R2002, performance and reliability enhanced).
07KR51: Commercial designation for AC31 basic unit with 8DI/6RelayDO.
Technical Parameters
Series: ABB Advant Controller 31 (AC31), Advant OCS compatible.
Inputs: 8 × 24 V DC digital inputs, sink/source compatible, ≤5 mA per channel, input delay 1–7 ms.
Outputs: 6 × relay outputs, rated 2 A @ 24 V DC / 120 V AC / 230 V AC, mechanical life ≥10⁶ operations.
Power Supply: 120/230 V AC ±10%, 47–63 Hz, 5 W (base) / 10 W (with expansion).
Processor: 400 KHz core; 64 KB battery‑buffered program/data memory.
Counters: 2 × hardware high‑speed counters (up to 5 kHz).
RTC: Integrated real‑time clock for time stamping and scheduling.
Operating Temperature: 0 °C to +55 °C; storage −40 °C to +70 °C.
Protection Class: IP20 (cabinet mounting).
Mounting: Standard DIN rail or screw mounting.
Dimensions: 127 mm × 102 mm × 127 mm; weight approx. 0.9 kg.
Certifications: CE, UL; manufactured in Sweden.
Interface and Communication Configuration
I/O Terminals: Screw terminals for 8 inputs, 6 relay outputs, and AC power terminals.
Programming Port: RS‑232 for programming, ASCII, or Modbus RTU communication.
System Bus: Integrated CS31 (RS‑485) bus, supports up to 31 remote I/O devices (total ~1000 I/O points).
LED Indicators: PWR, RUN, ERR, and channel‑status LEDs for diagnostics.
Expansion: Compatible with AC31 I/O modules (analog/digital) for system expansion.
Core Functions
Integrated Logic Control: Combines 8 digital inputs and 6 relay outputs for direct connection to sensors, switches, and actuators.
Deterministic Communication: CS31 bus enables long‑distance, high‑speed data exchange with remote I/O without reducing CPU scan performance.
High‑Speed Counting: Two hardware counters handle pulse counting and frequency measurement for motion/process applications.
Data Retention: Battery‑buffered memory preserves user program and data during power loss.
Diagnostics & Status: Channel‑level fault detection and LED indication for fast troubleshooting.
Enhanced Revision Features: R2002 revision improves EMC performance, communication stability, and thermal management.
Application Scenarios
Factory automation: Small production lines, assembly machines, and material handling equipment.
Building & HVAC: Chiller plants, air handling units, and environmental monitoring systems.
Water & wastewater: Pump control, valve sequencing, and level/flow monitoring.
Infrastructure: Lighting control, access systems, and distributed utility monitoring.
OEM machinery: Packaging, textile, and plastic processing equipment as a compact PLC core.
Operation and Maintenance Instructions
Installation: Mount vertically on DIN rail; maintain ≥50 mm clearance top/bottom for cooling; avoid vibration and direct moisture.
Wiring: Use AWG 14–24 copper wire; tighten terminals to 0.8 N·m; verify 120/230 V AC polarity and relay‑load voltage ratings.
Configuration: Program via ABB AC31GRAPH or 907AC1131 software; set I/O parameters, communication protocols, and counter functions.
Maintenance: Inspect terminal tightness and LED status quarterly; keep enclosure clean and free of dust/corrosive gases; replace backup battery every 3–5 years.
Safety: Disconnect power before servicing; do not operate with open covers or damaged wiring.
Get a Quote