ABB 07KT98‑S(GJR5253100R0260)safety‑certified CPU
May 29, 2026

ABB 07KT98‑S(GJR5253100R0260)safety‑certified CPU

ABB 07KT98‑S is a safety‑certified CPU in the Advant Controller AC31‑S (Safety) series, based on the standard 07KT98 platform. It retains the high‑performance 32‑bit RISC architecture, large memory, and high‑density mixed I/O of 07KT98, while adding functional safety compliance (SIL 2/PL d) and safety‑related I/O circuits for safety‑critical applications. The variant 07KT98‑S‑ARCNET (GJR5253100R0260) integrates ARCNET for real‑time safety networking, making it ideal for emergency stop, safety door, and process safety control in harsh industrial environments.

Description

Product Introduction

ABB 07KT98‑S is a safety‑certified CPU in the Advant Controller AC31‑S (Safety) series, based on the standard 07KT98 platform. It retains the high‑performance 32‑bit RISC architecture, large memory, and high‑density mixed I/O of 07KT98, while adding functional safety compliance (SIL 2/PL d) and safety‑related I/O circuits for safety‑critical applications. The variant 07KT98‑S‑ARCNET (GJR5253100R0260) integrates ARCNET for real‑time safety networking, making it ideal for emergency stop, safety door, and process safety control in harsh industrial environments.

Model Explanation

  • 07: Procontic 90 / AC31 series platform

  • KT: CPU with DC transistor outputs

  • 98: High‑capacity basic controller grade

  • ‑S: Safety‑certified variant (SIL 2/PL d, safety I/O & logic)

  • ‑ARCNET: Onboard ARCNET for safety‑related real‑time communication

Technical Parameters

  • Part Number: GJR5253100R0260

  • Processor: 32‑bit RISC (same as 07KT98)

  • Power Supply: 24 VDC (18–30 VDC), ≤22 W, reverse polarity protection

  • Memory: 1 MB Flash (program); 1 MB RAM (data); 256 kB non‑volatile RETAIN (safety recipes/critical data)

  • Onboard Digital I/O: 24 × 24 VDC DI (isolated, 3 groups); 16 × transistor DO (24 VDC/0.5 A, isolated, 2 groups, short‑circuit protected)

  • Safety I/O: Dedicated safety‑related DI/DO for SIL 2/PL d circuits (emergency stop, safety interlocks)

  • Onboard Analog I/O: 8 × 12‑bit AI (configurable 0–10 V/±10 V/4–20 mA/PT100); 4 × 12‑bit AO (configurable 0–10 V/4–20 mA)

  • High‑Speed Counter: 2 × 50 kHz (hardware, 7 modes)

  • Safety Certification: SIL 2 (IEC 61508), PL d (EN ISO 13849‑1)

  • Operating Temperature: 0°C to +55°C (standard industrial; extended ‑25°C to +70°C on request)

  • Storage Temperature: -40°C to +85°C

  • Protection Class: IP20

  • Dimensions: 180 × 100 × 95 mm

  • Weight: ≈1.0 kg

  • Certifications: CE, UL, CSA, RoHS, safety‑related EMC compliance

Interface & Communication Configuration

  • ARCNET: Onboard (standard) for deterministic safety networking (real‑time safety data exchange)

  • COM1: RS‑232 for programming, HMI, safety data logging

  • COM2: RS‑485 for Modbus RTU, CS31 system bus (safety I/O expansion)

  • CS31 System Bus: Up to 31 remote I/O slaves (including safety I/O modules)

  • Ethernet: Optional 10/100 Mbps for non‑safety communication (Modbus TCP/IP)

  • Safety Protocol: ARCNET for safety‑critical data (redundant, deterministic)

  • LED Indicators: PWR, RUN, ERR, SAFE (safety status), TX/RX (RS‑485), NET (ARCNET)

  • Programming Tool: Control Builder AC31 + Safetyconf (safety logic configuration)

  • RTC: Integrated for safety event time‑stamping

  • Storage: SmartMedia card for program/safety logic backup

Core Functions

  1. Functional Safety (SIL 2/PL d): Dedicated safety I/O and logic for emergency stop, safety doors, and process safety; certified per IEC 61508/EN ISO 13849‑1.

  2. Large Safety‑Optimized Memory: 1 MB program + 1 MB data + 256 kB RETAIN supports complex safety algorithms and recipe storage.

  3. High‑Density Mixed I/O: 24DI/16DO + 8AI/4AO plus dedicated safety I/O for integrated safety and standard control.

  4. Deterministic ARCNET Safety Network: Onboard ARCNET for real‑time, redundant safety communication between controllers.

  5. Multi‑Protocol Comms: ARCNET (safety), Ethernet (non‑safety), Modbus RTU, CS31 for seamless integration.

  6. Safety Data Retention: 256 kB RETAIN preserves safety‑critical data during power cycles.

  7. Safetyconf Configuration: Dedicated software for safety logic setup, validation, and diagnostics.

Application Scenarios

  • Safety‑Critical Process Control: Chemical, oil/gas, pharmaceutical plants (SIL 2/PL d safety loops).

  • Machine Safety: Packaging, automotive assembly, robotics (emergency stop, safety interlocks).

  • Distributed Safety Systems: Factory‑wide safety networks via ARCNET, remote safety I/O monitoring.

  • Legacy Safety System Upgrades: Replacing older AC31 safety CPUs with higher memory/performance.

  • Water/Wastewater Safety: Pump station interlocks, overflow protection, emergency shutdowns.

Usage & Maintenance Instructions

  • Installation: DIN rail mount; 50 mm clearance for ventilation; separate safety/standard wiring.

  • Wiring: Shielded cables for ARCNET/Ethernet; safety I/O cables routed separately; torque terminals 0.5–0.8 Nm.

  • Power‑On Check: Verify 24 VDC; PWR LED steady on; SAFE LED green (safety logic OK); ERR LED off.

  • Programming: Use Control Builder AC31 + Safetyconf; download safety logic via ARCNET/Ethernet; validate safety logic before deployment.

  • Routine Maintenance: Quarterly safety I/O continuity check; clean vents every 6 months; monitor SAFE/ERR LEDs.

  • Troubleshooting: SAFE LED red = safety fault (check interlocks/wiring); ARCNET faults = verify cables/addresses; I/O errors = check safety sensor/actuator wiring.

  • Environment: Operate 0°C to +55°C, 5%–95% non‑condensing humidity; avoid corrosive gases.

  • Replacement: Disconnect power; use identical 07KT98‑S; reconfigure safety logic/ARCNET parameters via Safetyconf.


Get a Quote