ABB 07KT98(GJR5253100R0278)high‑capacity basic controller (CPU)
May 29, 2026

ABB 07KT98(GJR5253100R0278)high‑capacity basic controller (CPU)

ABB 07KT98 is a high‑capacity basic controller (CPU) in the Advant Controller 31 (AC31) / Procontic CS31 series, serving as a core unit for medium‑to‑large automation systems. Compared with the 07KT97 series, it provides 1 MB program memory + 1 MB data memory + 256 kB RETAIN memory, larger onboard I/O, and native ARCNET/Ethernet options for networked control. Designed for complex process control, it supports standalone and distributed architectures with enhanced real‑time performance and data retention for critical industrial applications.

Description

Product Introduction

ABB 07KT98 is a high‑capacity basic controller (CPU) in the Advant Controller 31 (AC31) / Procontic CS31 series, serving as a core unit for medium‑to‑large automation systems. Compared with the 07KT97 series, it provides 1 MB program memory + 1 MB data memory + 256 kB RETAIN memory, larger onboard I/O, and native ARCNET/Ethernet options for networked control. Designed for complex process control, it supports standalone and distributed architectures with enhanced real‑time performance and data retention for critical industrial applications.

Model Explanation

  • 07: Procontic 90 / AC31 series platform

  • KT: CPU with DC transistor outputs

  • 98: High‑capacity basic controller grade (max memory & I/O)

  • (No suffix): Standard ARCNET/Ethernet enabled variant

Technical Parameters

  • Part Number: GJR5253100R0278

  • Processor: 32‑bit RISC

  • Power Supply: 24 VDC (18–30 VDC), ≤20 W, reverse polarity protection

  • Memory: 1 MB Flash (program); 1 MB RAM (data); 256 kB non‑volatile RETAIN (recipes/cumulative values)

  • Onboard Digital I/O: 24 × 24 VDC DI (sink/source, isolated, 3 groups of 8); 16 × transistor DO (24 VDC/0.5 A, isolated, 2 groups of 8, short‑circuit protected)

  • Onboard Analog I/O: 8 × 12‑bit AI (configurable 0–10 V/±10 V/4–20 mA/PT100 2/3‑wire); 4 × 12‑bit AO (configurable 0–10 V/4–20 mA)

  • High‑Speed Counter: 2 × 50 kHz (hardware, 7 modes)

  • Operating Temperature: 0°C to +55°C (standard industrial)

  • Storage Temperature: -40°C to +85°C

  • Protection Class: IP20

  • Dimensions: 180 × 100 × 95 mm

  • Weight: ≈1.0 kg

  • Certifications: CE, UL, CSA, RoHS

Interface & Communication Configuration

  • COM1: RS‑232 for programming, HMI, ASCII

  • COM2: RS‑485 for Modbus RTU master/slave, CS31 bus

  • CS31 System Bus: Up to 31 remote I/O slaves

  • ARCNET: Onboard (standard) for high‑speed real‑time networking

  • Ethernet: Optional 10/100 Mbps (model dependent) for Modbus TCP/IP, HTTP

  • Extension Port: For Profibus‑DP, additional comms modules

  • LEDs: PWR, RUN, ERR, TX/RX (RS‑485), NET (ARCNET/Ethernet)

  • Programming Tool: 907AC1131 (V4.1+ for ARCNET)

  • RTC: Integrated for data logging/time‑stamping

  • Storage: SmartMedia card for program/data backup

Core Functions

  1. Large Memory Capacity: 1 MB program + 1 MB data + 256 kB RETAIN supports complex algorithms, PID loops, and recipe storage.

  2. Native ARCNET/Ethernet: High‑speed deterministic networking for distributed control and remote monitoring.

  3. High‑Density Mixed I/O: 24DI/16DO + 8AI/4AO for analog/digital control in process and manufacturing.

  4. Dual 50 kHz Counters: For high‑speed encoders, flow meters, motion control.

  5. Multi‑Protocol Comms: ARCNET, Ethernet TCP/IP, Modbus RTU, CS31 for seamless system integration.

  6. Enhanced Data Retention: 256 kB RETAIN preserves critical data during power cycles.

  7. SmartMedia Backup: Easy program/data backup/restore via external card.

Application Scenarios

  • Medium‑to‑Large Process Control: Chemical, water/wastewater, food/beverage, pharmaceutical plants.

  • Distributed Automation: Factory‑wide networks, production lines with remote I/O.

  • Legacy System Migration: Upgrading older AC31/Procontic systems needing more memory/networking.

  • High‑Reliability Manufacturing: Automotive assembly, packaging, textile machinery.

  • Energy & Utilities: Power generation, oil/gas, HVAC with complex control logic.

Usage & Maintenance Instructions

  • Installation: DIN rail mount; vertical orientation, 50 mm clearance for ventilation.

  • Wiring: Shielded cables for analog/Ethernet; separate power/signal wires. Torque terminals 0.5–0.8 Nm.

  • Power‑On Check: Verify 24 VDC; PWR LED steady on. Check NET LED for link status.

  • Programming: Use 907AC1131; download via RS‑232, CS31, or Ethernet. Back up to SmartMedia card regularly.

  • Routine Maintenance: Quarterly terminal tightness check; clean vents every 6 months. Monitor ERR LED (flashing = fault).

  • Troubleshooting: ARCNET/Ethernet faults: check cables, addresses, baud rates. I/O errors: verify sensor/actuator wiring and signal types.

  • Environment: Avoid moisture/corrosive gases. Operate 0°C to +55°C, 5%–95% non‑condensing humidity.

  • Replacement: Disconnect power; use identical 07KT98. Reconfigure network/comm parameters to match system.


Get a Quote