ABB 07KT94 (GJR5252100R3261) high‑performance digital‑only CPU basic unit in the Advant Controller 31 (AC31)/Procontic CS31 Series 90
Description
Product Overview
Model Definition
07: Procontic 90/31 / AC31 series
KT: CPU with transistor outputs (DC)
94: High‑end digital I/O grade (Series 90)
Technical Specifications
Part Number: GJR5252100R3261
Processor: 16‑bit Motorola 68HC11
Power Supply: 24 VDC (18–30 VDC), ≤10 W
User Memory:
Program: 28 kB Flash EPROM
Data: 4.4 kB non‑volatile RAM
Onboard I/O:
Digital Inputs: 24 × 24 VDC (sink/source)
Digital Outputs: 16 × transistor (24 VDC/0.5 A)
Analog I/O: None (digital‑only)
High‑Speed Counter: 1 × 50 kHz
Communication:
COM1: RS‑232 (programming/ASCII)
COM2: RS‑485 (Modbus RTU / CS31 bus)
CS31 Bus: Up to 31 remote I/O modules
Max Expansion: 744 DI / 496 DO / 96 AI / 48 AO
Real‑Time Clock: Integrated (event timestamping)
Operating Temperature: 0 °C to +55 °C
Dimensions (W×H×D): 160 × 100 × 95 mm
Weight: ~0.8 kg
Certifications: CE, UL, CSA, RoHS
Interface & Indicators
LEDs: PWR, RUN, ERR, TX, RX, channel status (per I/O)
RS‑232: Programming, HMI, point‑to‑point ASCII
RS‑485: Modbus RTU (master/slave), CS31 system bus
Programming Software: 907 PC 331 / Control Builder AC31
Core Functions
High‑Density Digital Control: 24DI/16DO for large discrete applications
Distributed I/O: CS31 bus master (31 slaves max)
Serial Communication: Modbus RTU, ASCII, CS31 protocols
High‑Speed Counting: 50 kHz input for pulse/encoder signals
Data Logging: RTC + non‑volatile memory, event timestamping
Key Differences from 07KT92/93
07KT92: 12DI/8DO + 4AI/2AO (mixed I/O, analog capable)
07KT93: 24DI/16DO, no analog, 10 kHz counter
07KT94: 24DI/16DO, no analog, 50 kHz high‑speed counter (fastest in KT9x)
Applications
Factory automation: Large assembly lines, material handling, packaging
Process control: Discrete manufacturing, bottling, textile machinery
Machine control: Woodworking, plastics, printing equipment
System migration: Upgrade legacy Procontic CS31 installations
Installation & Maintenance
Mounting: 35 mm DIN rail or panel mount
Wiring: Shielded twisted pair for RS‑485/CS31
Backup: Use 07LE90 memory module for program backup
Maintenance: Annual program backup; periodic LED status check
Protection: Reverse‑polarity protection on power terminals; short‑circuit protection per DO channel