ABB 07KP90 (AC31 Series) high‑performance RCOM communication processor
Description
Product Introduction
Model Explanation
07: AC31/Procontic 90 series platform
KP: Communication Processor (RCOM protocol)
90: Hardware version and functional variant
Ordering Number: GJR5251000R0303 (standard part)
Technical Parameters
Power Supply: 24 VDC ±10% (19.2–30 VDC)
Current Consumption: ~105 mA typical
Communication Protocol: ABB proprietary RCOM (Remote Communication)
Physical Interface: RS‑485 (2‑wire), isolated
Network Topology: Multi‑drop, up to 32 slaves per master
Baud Rate: 300–19200 bps (configurable)
Isolation: 500 VAC between communication and backplane
Operating Temperature: -20 °C to +60 °C
Storage Temperature: -40 °C to +75 °C
Mounting: 35 mm DIN rail or AC31 rack slot
Dimensions (W×H×D): 51 × 254 × 152 mm
Weight: Approx. 0.4 kg
Certifications: CE, UL, RoHS compliant
Interface and Communication Configuration
Connector: Two DB9 ports (RCOM1/RCOM2) for RS‑485
RCOM Modes: Master (controls network) / Slave (responds to master)
Termination: Built‑in 120 Ω termination resistor (DIP switch)
LED Indicators:
RUN (green): Power and module OK
COMM (yellow): Data activity
ERR (red): Fault/communication error
Wiring: Shielded twisted pair (STP) recommended; separate from high‑power cables
Core Functions
RCOM Master/Slave Communication: Links AC31, Procontic T200, and MasterPiece 200 controllers.
Distributed I/O Networking: Connects remote RCOM I/O stations to central AC31 CPU.
Legacy System Bridge: Enables migration from older ABB systems to modern AC500 while preserving RCOM links.
Long‑Distance Communication: Supports leased lines, dedicated cables, and dial‑up modems for wide‑area connectivity.
Network Diagnostics: LED status and AC31 system diagnostics for fast fault localization.
Application Scenarios
AC31 System Expansion: Adding RCOM ports to AC31 PLCs for legacy device connection.
Factory Floor Integration: Interconnecting Procontic T200 and AC31 controllers in production lines.
Legacy Upgrade Projects: Migrating MasterPiece 200 systems to AC31/AC500 without replacing field wiring.
Process Automation: Distributed control in water treatment, power, and chemical plants.
Remote Monitoring: RCOM over modem links for remote site supervision.
Usage and Maintenance Instructions
Installation: Mount on 35 mm DIN rail or insert into AC31 rack; ensure proper grounding and ventilation.
Wiring: Connect 24 VDC; use STP for RS‑485; enable termination only at bus ends.
Configuration: Set master/slave mode, node address, and baud rate via AC31 programming software.
Routine Check: Verify LED status quarterly; inspect terminals and shielding annually.
Troubleshooting: Check power and wiring; confirm termination and address settings; reconfigure if errors persist.
Get a Quote