Reliance 45C-362
Description
Model Explanation
45C: General prefix for the control components of the Ryan AutoMate 45C series.
362: Represents an 8-channel analog output module.
Connector: The conventional way of writing the part number for industrial accessories. 45C-362 and 45C362 are the same product, with exactly the same performance and compatibility.
Version Description: There is no standard letter suffix to distinguish the revised models. Different production batches are distinguished by the serial number. Technical Specifications
Module type: Analog output module
Number of channels: 8 independent output channels
Output signal: Default 0–10 volts DC, configurable as 4–20 milliamps
Resolution: 12 bits
Isolation performance: Electrical isolation between analog side and logic side
Terminal connections: 20-pin detachable screw terminals for on-site wiring
Power supply from backplane: 5-volt DC power provided by the frame backplane
Occupied slot: Compatible with 45C series frame, occupying 1 standard slot
Weight: Approximately 0.84 kilograms
Operating temperature: 0 degrees Celsius to 55 degrees Celsius
Compatible devices: AutoMate 20/20E, AutoMax programmable logic controller, and 45C series I/O frame
Interface and configuration
Module installation: After cutting off the system power, install the module into the standard 45C series frame and tighten the fixing screws.
Output type selection: Select 0–10 volts DC or 4–20 milliamps output mode for each channel through the onboard dip switch.
Calibration function: Each channel is equipped with zero and range potentiometers, supporting on-site precision adjustment.
Status indication: The front panel is equipped with indicator lights, showing power, operation, and fault status respectively.
Main functions
Perform analog-to-digital conversion, output 0–10 volts DC or 4–20 milliamps signals, driving on-site actuators.
8 channels can be independently controlled, driving multiple on-site devices simultaneously.
Has electrical isolation capability, enhancing equipment's anti-interference ability, avoiding damage caused by surge voltage.
Output accuracy calibration can be completed through onboard potentiometers or PLC program. Application scenario
Used for the control of valves, frequency converters, and proportional valves in production lines.
Applied to the analog output control of temperature, pressure, flow, etc. in process industries.
As spare parts for the old AutoMate and AutoMax series PLC systems, it completes equipment replacement and daily maintenance.
Installation and operation instructions:
Installation: The module must be unplugged and plugged in while the power is off. Ensure good contact of the backplane and secure the screws in place.
Cable requirements: Use shielded twisted-pair cables for analog signals. Connect the shield layer to one end only and reduce signal interference.
Parameter configuration: Before powering on, select the output type through the code switch and complete zero point and range calibration.
Daily inspection: Regularly check the status of indicator lights and the tightness of terminals, keep the module clean, and prevent dust accumulation.
Get a Quote