Reliance 45C344
May 28, 2026

Reliance 45C344

The 45C344 is an 8‑channel analog input module for Reliance AutoMate 30/40 series PLCs, accepting ±10 VDC (bipolar) signals from sensors/transmitters. It converts analog signals to digital data for the CPU. Discontinued; only refurbished, surplus, or NOS units are available for legacy system maintenance.

Description

Product Description

The 45C344 is an 8‑channel analog input module for Reliance AutoMate 30/40 series PLCs, accepting ±10 VDC (bipolar) signals from sensors/transmitters. It converts analog signals to digital data for the CPU. Discontinued; only refurbished, surplus, or NOS units are available for legacy system maintenance.

Model Number Interpretation

  • 45C: Reliance AutoMate 45C‑series control components prefix.

  • 344: 8‑channel ±10 VDC bipolar analog input module.

  • No suffix: Original revision; no common A/B/C/D variants.

Technical Specifications

  • Channels: 8 single‑ended (differential configurable)

  • Input Range: ±10 VDC (bipolar, fixed)

  • Resolution: 12‑bit ADC

  • Conversion Rate: ~10 ms/channel

  • Accuracy: ±0.1% full scale (25°C)

  • Input Impedance: >1 MΩ

  • Backplane Power: 5 VDC, 200 mA

  • Slot Occupancy: 1 slot

  • Operating Temperature: 0°C to +55°C

  • Dimensions: ~96.5 × 70.5 × 56.5 mm

  • Weight: ~0.45 kg

  • Isolation: Channel‑to‑backplane 500 Vrms

Interface & Configuration

  • Mounting: Side‑insertion into 45C31x racks, screw‑secured.

  • Backplane: Edge connector for power/data/status.

  • Front Panel: ACTIVE/READY LEDs; no per‑channel indicators.

  • Terminal Block: 16‑pin removable screw terminal (signal ±, shield).

  • Configuration: Range fixed ±10 VDC; scaling/filtering via PLC software.

Core Functions

  • Converts ±10 VDC bipolar analog signals (pressure, level, temperature, flow) to 12‑bit digital values.

  • Provides 8 isolated channels for high noise immunity.

  • Transmits data to CPU via backplane.

  • Supports scaling/filtering via PLC programming.

  • Detects open/short/overvoltage faults; reports to CPU.

Application Scenarios

  • Analog input expansion for AutoMate 30/40 series racks.

  • Legacy systems: manufacturing, process control, water treatment, HVAC.

  • Monitoring ±10 VDC sensors (common in industrial instrumentation).

  • High‑density analog input applications (8 channels/slot).

Usage & Maintenance

  • Installation: Power off rack, insert module, tighten screws.

  • Wiring: Shielded cable; ground shield at one end.

  • Configuration: Set scaling in PLC software.

  • Routine Check: Verify ACTIVE/READY LEDs monthly; clean terminals quarterly.

  • Safety: Disconnect AC power before removal.


Get a Quote