Reliance 45C332
Description
Product Description
Model Number Interpretation
45C: Prefix for Reliance AutoMate 45C-series control components.
332: Designates a 10-slot dual fan module.
No suffix: Original hardware revision; no common lettered variants (A/B/C/D) for this part.
Technical Specifications
Input Voltage: 120 VAC, 50/60 Hz
Current Draw: 0.36 A
Configuration: Dual fans (parallel airflow)
Rack Compatibility: AutoMate 10-slot 45C31x series racks
Slot Occupation: 1 slot (replaces a blank filler panel)
Operating Temperature: 0°C to +55°C
Dimensions: ~96.5 × 70.5 × 56.5 mm
Weight: ~0.55 kg
Protection: Overcurrent fuse, fan fail alarm (via backplane)
Interface & Installation
Mounting: Side-insertion into standard AutoMate rack slots, secured with screws.
Backplane Connection: Edge connector for power and fan status signaling.
Front Panel: No user controls; integrated status LED (power/fan ok).
Airflow: Draws cool air from front, exhausts rear; aids convection for adjacent modules.
Core Functions
Delivers forced-air cooling to prevent overheating in 10-slot racks with high power dissipation.
Maintains optimal temperature for CPU, power supply, and I/O modules during continuous operation.
Monitors fan operation and reports faults to the PLC backplane for system diagnostics.
Reduces thermal stress on components, extending service life of legacy systems.
Application Scenarios
Cooling upgrade/replacement for 10-slot AutoMate 30/40 series PLC racks.
Maintenance of legacy industrial systems (manufacturing lines, process control, water treatment, metallurgy).
High-density I/O racks where passive cooling is insufficient.
Critical control panels requiring reliable thermal management for long-term operation.
Usage & Maintenance
Installation: Power off the rack, remove the blank panel, insert 45C332, and tighten screws.
Wiring: No external wiring; power is drawn directly from the backplane.
Routine Check: Verify fan rotation and status LED monthly; clean dust from fan blades quarterly.
Replacement: If a fan fails, replace the entire module (fans are not field-replaceable).
Safety: Disconnect AC power before removal to avoid electric shock.