Reliance 2GU41040
Description
Product Description
Model Number Interpretation
2: Standard industrial drive series
GU: GP‑2000 series, 460 VAC voltage class
41040: 4 = 460 VAC; 1040 = 40 HP; hardware revision 40
Technical Specifications
Rated Motor Power: 40 HP (30 kW)
Apparent Power: 52 kVA
Input: 460 VAC ±10%, three‑phase, 50/60 Hz; max 78 A
Output: 0–460 VAC, three‑phase; continuous 65 A, max 65 A; frequency 0–400 Hz
Control Mode: Open‑loop V/F (Volts‑per‑Hertz)
Protection: Overcurrent, overvoltage, undervoltage, overtemperature, short‑circuit, ground fault, electronic motor overload
Enclosure: NEMA 1 (indoor) or chassis style
Ambient Temperature: 0 °C to +45 °C
Dimensions (H×W×D): approx. 600 × 350 × 320 mm
Weight: approx. 45 kg
Certifications: UL listed, IEC certified, CSA certified
Interface and Communication Configuration
Power Terminals: Three‑phase input, motor output, DC bus braking connection
Control Terminals: ±10 V analog input (speed reference); 24 VDC digital I/O for start/stop, fault reset, jog operation, multi‑speed selection
Communication: Reliance proprietary protocol; no standard fieldbus (e.g., Modbus, Profibus)
Operator Interface: Built‑in keypad with 7‑segment LED display for parameter setup, status monitoring, and fault code readout
Encoder Interface: None (open‑loop control only)
Core Functions
Stable V/F speed regulation for 40 HP three‑phase AC motors
Energy saving for variable‑torque loads (fans, pumps)
Electronic reversing: reverse from any motor speed without contactors
Automatic/manual torque boost for heavy starting loads
Three preset speeds selectable via digital inputs
Adjustable current limit: 50–100% of rated output current
57 password‑protected programmable parameters; non‑volatile memory retains settings during power loss
Real‑time status monitoring and fault code logging for quick diagnostics
Compatibility with external braking resistors for rapid deceleration
Application Scenarios
Light & heavy industry: Conveyors, packaging machines, assembly lines, mixers, extruders
HVAC & process: Large fans, water pumps, cooling towers, agitators
Material handling: 40 HP motor‑driven conveying, lifting, and hoisting equipment
Legacy automation: Direct replacement for GP‑2000 series drives in existing systems
Usage and Maintenance Instructions
Install in a well‑ventilated cabinet; maintain minimum 100 mm clearance around the drive for heat dissipation
Use shielded cables for power and control wiring; tighten all terminals to specified torque
Verify input voltage before powering on; energize control circuit first, then main power
Set parameters per motor nameplate (voltage, current, base frequency, overload)
Quarterly maintenance: Inspect terminals for looseness or overheating, clean internal dust, check cooling fan operation
Before inspection/service: Disconnect all power and wait 5 minutes for DC bus capacitors to fully discharge
Avoid operating in condensing humidity or corrosive environments; keep ambient temperature within 0–45 °C
Get a Quote