Honeywell 51304650-100 (MU-TDOD13)
Description
Product Description
Model Definition
5130: Honeywell TPS/TDC3000/Experion PKS series
4650: Digital Output (DO) FTA family
100: HW revision R100, SSR, screw‑terminal version (MU‑TDOD13)
Technical Specifications
Channels: 16 DO, SSR type
Load Voltage: 3–30 VDC
Load Current: 2 A max per channel
Isolation: Channel‑to‑ground (no channel‑to‑channel)
Dielectric Strength: 1000 VAC, 1 minute
Backplane Power: 24 VDC ±10%
Power Consumption: ~3.9 W
Operating Temp: 0°C to +55°C
Storage Temp: -40°C to +85°C
Humidity: 5%–90% RH, non‑condensing
Terminals: Screw type
Weight: ~0.5 kg
Certifications: CE, UL
Interface & Features
System: UCN backplane I/O bus
Field: 16× (Common / NO / NC) screw terminals
Diagnostics: Board‑level fault detection (no per‑channel)
Redundancy: Not supported
Hot Swap: Supported
Core Functions
SSR Switching: Fast, bounce‑free DC output for 24 VDC solenoids, indicators, small relays.
Screw Terminals: Easy field wiring, reusability.
Cost‑Effective: Entry‑level DC DO FTA for non‑redundant, basic needs.
51304650 Series Quick Compare (R100/R150/R200/R250)
| Feature | R100 (51304650‑100) | R150 (51304650‑150) | R200 (51304650‑200) | R250 (51304650‑250) |
|---|---|---|---|---|
| Model | MU‑TDOD13 | MC‑TDOD13 | MU‑TDOD13 | MC‑TDOD53 |
| Output | SSR (DC) | SSR (DC) | SSR (DC) | Relay (AC/DC) |
| Terminals | Screw | Compression | Screw | Screw |
| Voltage | 3–30 VDC | 3–30 VDC | 3–30 VDC | 250 VAC/30 VDC |
| Current | 2 A DC | 2 A DC | 2 A DC | 3 A AC/5 A DC |
| Isolation | Ch‑to‑GND | Ch‑to‑GND | Ch‑to‑GND | Ch‑to‑Ch+GND |
| Diagnostics | Board‑level | Board‑level | Board‑level | Per‑channel |
| Redundancy | No | No | No | Yes |
Applications
Systems: Honeywell TPS, TDC3000, Experion PKS (UCN)
Industries: Petrochemical, power, water treatment, manufacturing
Typical Loads: 24 VDC solenoid valves, lamp indicators, small contactors, alarm annunciators
Installation & Maintenance
Installation
Insert into standard DCS I/O slot
Secure backplane connector
Wire field devices to screw terminals
Configure in system software
Maintenance
Inspect terminals quarterly for tightness/oxidation
Verify SSR operation via system diagnostics
Store spares in anti‑static bags
Get a Quote