Honeywell 51304650-200 (MU-TDOD13)
Description
Product Description
Model Definition
5130: Honeywell TPS/TDC3000/Experion PKS DCS series
4650: Digital Output (DO) FTA family
200: Hardware revision R200, solid-state, low-voltage, cost-optimized version
Technical Specifications
Channels: 16 digital outputs (DO), SSR type
Output Rating: 3–30 VDC, 2 A max (per channel)
Isolation: Channel-to-ground isolation (no channel-to-channel isolation)
Dielectric Strength: 1000 VAC for 1 minute
Backplane Power: 24 VDC ±10%
Power Consumption: 4–6 W (typical)
Operating Temp: 0°C to +60°C
Storage Temp: -40°C to +85°C
Humidity: 10%–90% (non-condensing)
Weight: ~0.5 kg
Certifications: CE, UL
Interface & Features
System Connection: DCS backplane I/O bus
Field Terminals: 16 channels with common, NO, NC screw terminals
Diagnostics: Board-level fault detection (no per-channel diagnostics)
Redundancy: Not supported
Hot Swap: Supported
Core Functions
Solid-State Switching: Fast, bounce-free control of low-voltage devices (24 VDC solenoids, small relays, indicators)
Cost-Effective: Lower cost than R250 for basic DO needs
Space-Saving: 16-channel density reduces cabinet footprint
51304650-200 vs 51304650-250 (R200 vs R250)
| Feature | R200 (51304650-200) | R250 (51304650-250) |
|---|---|---|
| Output Type | Solid-State Relay (SSR) | Electromechanical Relay (SPDT) |
| Load Voltage | 3–30 VDC | 250 VAC / 30 VDC |
| Load Current | 2 A DC | 3 A AC / 5 A DC |
| Isolation | Channel-to-ground | Channel-to-channel + ground |
| Diagnostics | Board-level | Per-channel |
| Redundancy | No | Yes |
| Price | Lower | Higher |
Applications
Compatible Systems: Honeywell TPS, TDC3000, Experion PKS
Industries: Petrochemical, power, water treatment, general manufacturing
Typical Uses: 24 VDC solenoid valves, lamp indicators, small contactors, alarm annunciators
Installation & Maintenance
Installation
Insert into standard DCS I/O slot
Secure backplane connector
Wire field devices to corresponding terminals
Configure channel parameters in system software
Maintenance
Inspect terminals quarterly for looseness/oxidation
Verify SSR operation via system diagnostics
Store spares in anti-static packaging
Get a Quote