Honeywell 51304718-325 (51304718325)
May 28, 2026

Honeywell 51304718-325 (51304718325)

51304718-325 (also known as MU-GAIH83) is a Honeywell HLAI/STI series of isolated high-level analog input field terminal boards (FTA) specifically designed for TDC 3000, TPS, UCN, and Experion PKS DCS systems. As the connection interface between the field analog transmitters and the main control analog input module, it features crimp terminals and a PCB coated with three-layer anti-corrosion paint, with 1500VAC electrical isolation capability, suitable for harsh industrial environments, and is a non-redundant standard model.

Description

Product Introduction

51304718-325 (also known as MU-GAIH83) is a Honeywell HLAI/STI series of isolated high-level analog input field terminal boards (FTA) specifically designed for TDC 3000, TPS, UCN, and Experion PKS DCS systems. As the connection interface between the field analog transmitters and the main control analog input module, it features crimp terminals and a PCB coated with three-layer anti-corrosion paint, with 1500VAC electrical isolation capability, suitable for harsh industrial environments, and is a non-redundant standard model.

Model Interpretation

5130: represents the Honeywell TDC 3000/UCN distributed control system series;

4718: refers to the category of high-level analog input field terminal boards (FTA) with electrical isolation;

325: hardware version identifier, representing the non-redundant, crimp terminals, and PCB coated with three-layer anti-corrosion paint configuration, distinct from the redundant version 375. Technical Specifications

Channel Configuration: 8 differential analog input channels;

Supported Signals: 4-20mA current, 1-5VDC/0-10VDC voltage standard high-level signals;

Isolation Performance: 1500VAC RMS electrical isolation between the field side and the system side;

Interface Specifications: Press-fit terminals on the field side, 50-pin flat cable interface on the system side;

Measurement Accuracy: ±0.1% of full scale at 25℃ environment;

Environmental Conditions: Operating temperature -20℃ to +60℃, storage temperature -40℃ to +70℃, relative humidity 5% to 95% (no condensation);

Protection Certification: Circuit board coated with three-layer anti-corrosion paint, CE, UL, CSA, RoHS certified;

Structural Weight: Size B specification, approximately 1.2kg (non-redundant design).

Interface and Communication Configuration

System Connection: Through 50-pin dedicated flat cable, compatible with MC-PAIH03, 51304754-150 and other high-level analog input modules;

Field Wiring: 8 pairs of press-fit terminals, connecting 4-20mA/1-5VDC pressure, temperature, level, flow, etc. field transmitters;

Isolation Design: Field wiring is completely electrically isolated from the internal circuits of the DCS, eliminating ground loops and electromagnetic interference;

Communication Characteristics: Passive terminal components, no independent communication protocol, signal processing, analog conversion and fault diagnosis are completed by the matching input module and the DCS network. Core function

Signal Access: Achieve terminal access and transfer of 8 channels of on-site high-level analog signals;

Electrical Isolation: 1500VAC isolation protection to prevent transient voltages and grounding faults from damaging the core equipment of the DCS;

Environmental Adaptability: Three-proof paint circuit boards are suitable for humid, dusty, and corrosive working conditions, and the crimp terminals are resistant to vibration and have stable connections;

System Compatibility: Fully compatible with TDC 3000, TPS, UCN, and Experion PKS systems, supporting hot swapping and on-site quick replacement;

Non-redundant Design: Meet the high-reliability signal acquisition requirements in general working conditions, with better cost performance than redundant models. Applicable scenarios

Adaptation system: Honeywell TDC 3000, TPS, UCN, Experion PKS distributed control systems;

Industry applications: Process industries such as oil and gas, chemical, petrochemical, power generation, pharmaceuticals, papermaking, etc.;

Signal adaptation: Connect to output 4-20mA/1-5VDC pressure, temperature, level, and flow transmitters;

Installation environment: DCS control cabinet, on-site control panel, suitable for industrial sites with high humidity, dust, and corrosive gases.

Usage and maintenance instructions Use

Installation: Securely attach to a standard DCS cabinet, leaving sufficient space for wiring and heat dissipation;

Wiring: Plug in the 50-pin flat cable firmly and lock it in place. For the on-site transmitters, connect the cables to the press-fit terminals according to the specifications to ensure a secure connection;

Power-on and Debugging: After wiring is completed, start the DCS and check for no fault alarms. Verify the accuracy of the on-site signal reading before putting it into operation. Maintenance

Environmental Maintenance: Keep the cabinet clean and well-ventilated, and avoid prolonged exposure to damp and corrosive substances;

Regular Inspection: Check the connection status of terminals and cables every quarter, and replace damaged components in time;

Cleaning and Protection: Use a dry soft cloth to wipe off surface dust; Do not allow liquid cleaners or abrasive tools to come into contact with the circuit board and terminals;

Storage and Anti-static: Store spare parts in anti-static bags and place them in a cool and dry place; Take anti-static measures during handling to prevent damage from static electricity to components;

Prohibition of Self-Dismantling: Non-professionals are not allowed to disassemble the equipment to prevent damage to the internal circuits.


Get a Quote