HONEYWELL 51304728-325
Description
Product Description
Model Definition
5130: TDC 3000/UCN DCS series.
4728: Digital Input FTA with galvanic isolation.
325: 32 channels, non‑coated PCB, crimp terminals, CE compliant, supports redundancy.
Technical Specifications
Channels: 32 digital input channels.
Signal Types: 24 VDC dry contact / active signals; 120 VAC (with MTL 4013 barrier).
Isolation: 250 VAC RMS galvanic isolation (field‑to‑system).
Terminals: Crimp‑style (field); 50‑pin ribbon connector (system).
Input Ratings: 10.5 Vdc max, 14 mA Isc max, 800 Ω min source resistance.
Operating Temperature: -20°C to +60°C.
Storage Temperature: -40°C to +70°C.
Humidity: 5%–95% non‑condensing.
PCB Coating: Non‑conformal coated.
Certifications: CE, UL, CSA, RoHS.
Form Factor: Size B (307 mm), weight approx. 1.8 kg.
Interface and Communication Configuration
System Side: Connects to digital input IOPs (e.g., MC‑PDI02, 51304446‑150) via 50‑pin ribbon cable.
Field Side: 32 crimp terminals for discrete devices (switches, relays, proximity sensors).
Isolation: Full galvanic isolation eliminates ground loops and transient voltages.
Redundancy: Supports dual‑module redundancy for high‑availability architectures.
Protocol: Passive FTA; no independent protocol. All processing/diagnostics via IOP and DCS.
Core Functions
Provides 32‑channel isolated digital input termination for 24 VDC/120 VAC field devices.
250 VAC isolation protects DCS from noise, spikes, and ground faults.
Non‑coated PCB for clean, dry industrial environments.
Internal filtering and surge protection improve signal integrity and reliability.
Crimp terminals ensure vibration resistance and consistent connections.
Drop‑in compatible with TDC 3000/TPS/UCN/Experion PKS; hot‑swap capable.
Application Scenarios
Systems: Honeywell TDC 3000, TPS, UCN, Experion PKS DCS.
Industries: Oil & gas, chemical, power, pharmaceutical, pulp & paper, general manufacturing.
Field Devices: Limit switches, pressure switches, level switches, proximity sensors, relay contacts.
Installation: Control room cabinets, clean/dry industrial panels (non‑corrosive, low dust).
Usage and Maintenance Instructions
Usage
Mount in standard DCS cabinet with clearance for wiring and airflow.
Connect 50‑pin ribbon cable to matching IOP; seat and lock firmly.
Crimp field wires to terminals per polarity; avoid over‑crimping.
Power on DCS, check for fault alarms, and verify input status before commissioning.
Maintenance
Maintain clean, dry, ventilated environment.
Inspect crimps and cables quarterly for tightness, corrosion, or damage.
Clean only with dry soft cloth—no liquids or abrasives.
Store spares in anti‑static bags in cool, dry area.
Use ESD protection during handling; do not disassemble.
Get a Quote