HONEYWELL 51304728-375
May 28, 2026

HONEYWELL 51304728-375

The 51304728-375 (also written as 51304728375) is a 16‑channel Galvanically Isolated Digital Input FTA (Field Terminal Assembly) for Honeywell TDC 3000, TPS, UCN, and Experion PKS DCS. It provides 1500 VAC isolation, signal filtering, and surge protection for 24 VDC digital input signals from field switches and sensors. Designed for harsh industrial environments, it features a conformally coated PCB and gold‑plated screw terminals.

Description

Product Description

The 51304728-375 (also written as 51304728375) is a 16‑channel Galvanically Isolated Digital Input FTA (Field Terminal Assembly) for Honeywell TDC 3000, TPS, UCN, and Experion PKS DCS. It provides 1500 VAC isolation, signal filtering, and surge protection for 24 VDC digital input signals from field switches and sensors. Designed for harsh industrial environments, it features a conformally coated PCB and gold‑plated screw terminals.

Model Definition

51304728-375 is Honeywell’s official part number.
  • 5130: Indicates TDC 3000/UCN DCS series.

  • 4728: Denotes Digital Input FTA with 16‑channel isolation.

  • 375: Specifies conformally coated PCB, 24 VDC input, screw terminals, and redundant compatibility.

    Also known as MU‑TDIA16 (16‑channel Digital Input FTA, GI/IS, coated).

Technical Specifications

  • Channels: 16 differential digital input channels.

  • Signal Type: 24 VDC dry contact or active high/low signals.

  • Isolation: 1500 VAC RMS galvanic isolation between field and system sides.

  • Terminals: Gold‑plated screw terminals (field wiring) and 50‑pin ribbon cable connector (system side).

  • Input Voltage: 24 VDC nominal, 18–30 VDC operating range.

  • Current Draw: ≤10 mA per channel.

  • Operating Temperature: -20°C to +60°C.

  • Storage Temperature: -40°C to +70°C.

  • Humidity: 5%–95% non‑condensing.

  • PCB Coating: Conformal coated (for harsh environments).

  • Certifications: CE, UL, CSA, RoHS.

  • Form Factor: Size B, weight approx. 1.2 kg.

Interface and Communication Configuration

  • System Side: Connects to digital input IOPs (e.g., MC‑PDI02, 51304446‑150) via a dedicated 50‑pin ribbon cable.

  • Field Side: 16 pairs of screw terminals for 24 VDC digital inputs (switches, relays, proximity sensors).

  • Isolation: Complete galvanic isolation blocks ground loops and transient voltages.

  • Redundancy: Supports dual‑module redundancy for high‑availability systems.

  • Protocol: Passive FTA; no independent communication protocol. All signal processing and diagnostics are handled by the connected IOP and DCS.

Core Functions

  • Provides 16‑channel isolated digital input termination for 24 VDC field devices.

  • 1500 VAC isolation protects DCS from electrical noise, ground loops, and voltage spikes.

  • Conformal coating ensures reliability in humid, dusty, or corrosive environments.

  • Internal filtering and surge protection enhance signal stability and device longevity.

  • Gold‑plated terminals resist oxidation and vibration, ensuring consistent connections.

  • Drop‑in compatible with TDC 3000/TPS/UCN/Experion PKS; supports hot‑swap replacement.

Application Scenarios

  • Systems: Honeywell TDC 3000, TPS, UCN, Experion PKS DCS.

  • Industries: Oil & gas, chemical, petrochemical, power generation, pharmaceutical, pulp & paper, mining.

  • Field Devices: Limit switches, pressure switches, level switches, proximity sensors, relay contacts.

  • Installation: DCS control room cabinets, local control panels, and harsh industrial environments (high humidity, dust, corrosive gases).

Usage and Maintenance Instructions

Usage

  • Mount the FTA in a standard DCS cabinet with adequate space for wiring and ventilation.

  • Connect the 50‑pin ribbon cable to the corresponding digital input IOP; ensure full insertion and locking.

  • Wire field devices to the designated terminals, observing polarity; tighten terminals to 0.8–1.0 N·m torque.

  • Power on the DCS, verify no fault alarms, and confirm input status accuracy via the system interface before operation.

Maintenance

  • Keep the environment clean, dry, and well‑ventilated.

  • Inspect terminals and cables quarterly for tightness, corrosion, or damage; replace worn components promptly.

  • Clean the PCB and terminals with a dry, soft cloth only; do not use liquids or abrasives.

  • Store spare units in anti‑static bags in a cool, dry area.

  • Use anti‑static wristbands and mats during handling to prevent ESD damage.

  • Do not disassemble the unit; repairs must be performed by authorized personnel.


Get a Quote