HONEYWELL 51304754-150(MC-PAIH03)
Description
Product Description
Model Definition
51304754-150: Official Honeywell part number; 5130 = DCS hardware series, 4754 = high-level analog input circuit, 150 = hardware revision.
MC-PAIH03: Product alias (High-Level Analog Input Processor).
Alternate P/N: 51304754150 (hyphen omitted).
Technical Specifications
Input Channels: 16 differential analog inputs.
Input Types: Voltage (e.g., 1–5 VDC), current (4–20 mA; 2-wire/self-powered transmitters).
CMRR: 70 dB (DC to 60 Hz, 500 Ω imbalance).
Power: 24 VDC ±10%, ≤10 W.
Isolation: 1500 VAC between field and system.
Operating Temp: -20°C to +60°C; Storage: -40°C to +70°C.
Humidity: 5%–95% (non-condensing).
Weight: ~0.58 kg; Dimensions: 313 × 278 × 30 mm.
Certifications: CE, UL, CSA, RoHS.
Interface & Communication
Connector: Gold finger for dedicated LCN rack slot.
FTA Compatibility: MU-TAIH02, TAIH12/52/03/13/23/53/22/62 (field terminal assemblies).
Indicators: LEDs for power, run, fault, and channel status.
Protocol: DCS proprietary; data rate up to 1 Mbps.
Core Functions
High-Level Signal Acquisition: Collect 16-channel voltage/current signals from transmitters.
Signal Conditioning: Amplify, filter, and isolate signals to suppress EMI.
Data Conversion: Convert analog signals to digital for DCS processing.
Diagnostics: Real-time channel monitoring, fault detection, and alarm reporting.
System Expansion: Increase DCS analog input capacity for complex processes.
Application Scenarios
Industries: Oil/gas, chemical, petrochemical, power, pharmaceutical.
Uses: Connect pressure, temperature, flow, level transmitters in TDC 3000/TPS cabinets.
Environments: Standard control rooms and field cabinets; system upgrades/replacements.
Usage & Maintenance
Usage
Insert into dedicated LCN slot and secure screws.
Connect field transmitters to FTA terminals.
Power on and verify LED status (power/run normal, no faults).
Configure input ranges and parameters via DCS engineer station.
Test signals and communication before operation.
Maintenance
Environment: Clean, dry, ventilated; temp/humidity within specs.
Inspection: Monthly LED check; quarterly cable tightness/integrity.
Cleaning: Wipe dust with dry cloth; no liquid cleaners.
Storage: Spare modules in anti-static bags, cool/dry area.
Repair: No unauthorized disassembly; replace faulty modules promptly.
Get a Quote