HONEYWELL 51305890‑175(MC‑TAMT04)
May 28, 2026

HONEYWELL 51305890‑175(MC‑TAMT04)

The 51305890‑175 is a Low‑Level Multiplexer FTA (LLMUX2 FTA) for Honeywell TDC 3000 and Experion PKS DCS, designed for high‑density thermocouple (TC) and millivolt signal input. It integrates 32 channels of low‑level signal conditioning, cold‑junction compensation (CJC), and channel‑to‑channel isolation. The conformal coated version (‑175) provides enhanced protection against dust, moisture, and mild corrosion for reliable operation in harsh industrial environments.

Description

Product Description

The 51305890‑175 is a Low‑Level Multiplexer FTA (LLMUX2 FTA) for Honeywell TDC 3000 and Experion PKS DCS, designed for high‑density thermocouple (TC) and millivolt signal input. It integrates 32 channels of low‑level signal conditioning, cold‑junction compensation (CJC), and channel‑to‑channel isolation. The conformal coated version (‑175) provides enhanced protection against dust, moisture, and mild corrosion for reliable operation in harsh industrial environments.

Model Definition

  • 51305890‑175: Honeywell part number (‑175 = conformal coated, CE‑compliant).

  • MC‑TAMT04: Formal model (MC=Control Component, TAMT=Thermocouple Analog Multiplexer, 04=revision).

  • Breakdown:

    • 5130: Honeywell DCS hardware series.

    • 5890: Low‑level multiplexer circuit design.

    • 175: Conformal coating for industrial environments.

Technical Specifications

  • System Compatibility: Honeywell TDC 3000, Experion PKS (C300).

  • Channel Count: 32‑channel thermocouple/mV input.

  • Signal Types: Thermocouple (J, K, T, E, R, S, B), ±100 mV, ±500 mV.

  • Resolution: 16‑bit per channel.

  • Accuracy: ±0.05% FS at 25 °C; fast open TC detection (<1 sec).

  • Isolation: 500 VDC channel‑to‑channel and channel‑to‑ground.

  • CJC: Onboard cold‑junction compensation with local reference.

  • Power Supply: 24 VDC ±10%, 0.4 A typical.

  • Operating Temperature: −20 °C to +60 °C.

  • Storage Temperature: −40 °C to +85 °C.

  • Humidity: 5%–95% RH, non‑condensing.

  • Dimensions: 307 mm × 220 mm × 30 mm (Size B, 12‑inch).

  • Weight: Approx. 0.75 kg.

  • Certifications: CE, UL, CSA, RoHS compliant.

  • Protection: Conformal coating (‑175) for dust/moisture resistance.

Interface and Communication Configuration

  • Front‑panel: 32‑channel compression screw terminals (secure TC/mV wiring), 24 VDC power/ground terminals.

  • Internal Bus: Ribbon cable to LLMux IOP (51304362‑150), Honeywell proprietary I/O bus, up to 10 Mbps.

  • Protocols: Honeywell I/O bus; supports HART pass‑through (with smart transmitters).

  • Diagnostics: Real‑time status (power, fault, comm); detects open/short, overrange, CJC errors.

Core Functions

  1. 32‑Channel Low‑Level Multiplexing: Multiplexes weak TC/mV signals into one high‑speed data stream for DCS.

  2. Precision Signal Conditioning: Amplifies, filters, isolates to reduce EMI/RFI; per‑channel A/D eliminates crosstalk.

  3. Cold‑Junction Compensation: Onboard CJC ensures accurate TC measurements, minimizes error.

  4. Fast Fault Detection: Open TC detection <1 sec; monitors loops for faults and triggers alarms.

  5. Hot‑Swap: Online replacement without shutdown; system auto‑recognizes module.

  6. Harsh Environment Protection: Conformal coating resists dust, moisture, mild corrosion.

Application Scenarios

Widely used in process industries: oil & gas, chemical, power generation, pharmaceutical, pulp & paper. Deployed in Honeywell DCS for:
  • High‑density temperature monitoring (furnaces, reactors, heat exchangers).

  • Data acquisition from TC/mV sensors in harsh industrial areas.

  • Critical process parameter monitoring in control rooms (−20 °C to +60 °C).

Usage and Maintenance Instructions

Usage

  1. Installation: Mount on 35 mm DIN rail or panel; ensure 50 mm ventilation clearance.

  2. Power Wiring: Connect 24 VDC ±10%; verify power LED on, no fault alarms.

  3. Field Wiring: Connect TC/mV sensors to 32‑channel terminals (observe polarity/TC type); torque screws to 0.8–1.0 Nm.

  4. System Configuration: Use DCS engineer station to set channel types (TC/mV), ranges, CJC parameters; download config and verify data.

  5. Hot‑Swap: Replace faulty module with identical model during operation; system resumes acquisition in <30 sec.

Maintenance

  1. Environment: Keep cabinet clean, dry, −20 °C to +60 °C; avoid direct sunlight, corrosive gases.

  2. Inspection: Monthly check LEDs (power/fault/comm); quarterly inspect terminals for looseness/corrosion.

  3. Cleaning: Wipe surface/connectors with dry soft cloth; no liquid cleaners/compressed air.

  4. Storage: Spare modules in anti‑static bags at −40 °C to +85 °C; avoid vibration/extreme temps.

  5. Safety: Do not disassemble; only qualified personnel to perform maintenance. Unauthorized disassembly voids warranty。


Get a Quote