GE469-P1-HI-A20-T-H Motor Management Relay Product Description
Description
GE469-P1-HI-A20-T-H Motor Management Relay Product Description
I. Product Introduction
GE469-P1-HI-A20-T-H is a high-performance microprocessor-based motor management relay from General Electric (GE), specifically designed for medium and high voltage as well as critical industrial applications. It integrates comprehensive protection, precise monitoring, flexible control, and intelligent communication functions, and can operate independently or be integrated into an automation system. It provides full lifecycle protection and operation support for industrial motors and is widely used in petrochemicals, power, mining, water treatment, and other fields.
II. Basic Information
Model: GE469-P1-HI-A20-T-H
Brand: General Electric (GE), affiliated with GE Digital Energy
Series: Multilin 469 Motor Management Relay Series
Type: Multi-function Motor Protection and Management Device
Target Application: Medium-sized and large AC motors (three-phase asynchronous motors, synchronous motors, etc.)
Installation Method: Standard DIN rail installation or panel installation
Protection Grade: IP20 (dust-proof, finger-proof)
Certifications: CE, UL, CSA, IEC 60255, etc. industrial certifications
Environmental Parameters: Operating temperature - 40°C to + 70°C, storage temperature - 40°C to + 85°C, relative humidity 5%–95% (no condensation)
Size: Approximately 200mm×156mm×101mm
Weight: Approximately 4.5kg
III. Electrical Specifications
Input Parameters
Working Power Supply: 70–265 VAC or 90–230 VDC, 50/60Hz adaptive
Current Input: 4–20A (compatible with CT secondary side), measurement accuracy ±1%
Voltage Input: 0–600V AC (compatible with PT secondary side), supports phase voltage, line voltage measurement
Temperature Input: Multiple RTD (platinum resistance) input, monitors motor stator, bearing temperature
Digital Input: Multiple programmable dry contact inputs, receives external start/stop, interlock signals
Output Parameters
Relay Output: 6 programmable relay contacts (normally open / normally closed), used for tripping, alarming, controlling contactors / circuit breakers
Analog Output: 4 programmable 4–20mA analog output, uploads parameters such as current, voltage, temperature to the upper computer
Communication Interface: Standard RS232/RS485, supports Modbus RTU, Profibus-DP protocols, optional Ethernet module
IV. Core Protection Functions
1. Overload Protection
Adaptive thermal model algorithm is used to monitor motor current and temperature in real time, simulates the thermal accumulation process of the motor, has inverse-time characteristics, avoids long-term overheating and burnout of the motor; supports dual setting value storage, can quickly switch different working condition protection parameters.
2. Short Circuit Protection
Instantaneous / short delay overcurrent protection, detects severe short circuit faults, action time ≤ 50ms, quickly cuts off power supply, prevents motor winding burnout and expansion of busbar faults.
3. Ground Fault Protection
Highly sensitive ground fault detection, can detect leakage faults as low as 5% of the rated current, compatible with direct grounding, resistance grounding systems, avoids personal electric shock and equipment insulation damage.
4. Stall / Overspeed Protection
When the motor starts with stall or runs at overspeed, quickly detects abnormal increase in current, timely trips for protection, prevents rotor jamming resulting in mechanical and electrical damage.
5. Voltage / Frequency Abnormal Protection
Overvoltage, undervoltage, undervoltage, phase sequence error, voltage imbalance, frequency abnormality (overfrequency / underfrequency) protection, avoids insulation aging, abnormal speed, vibration intensification and other faults of the motor due to power supply quality problems. 6. Temperature Protection
Real-time monitoring of the stator and bearing temperatures of the motor by RTD. When the temperature exceeds the limit, an alarm or trip occurs to prevent the motor from overheating and damage. Temperature thresholds can be programmed.
7. Other Protection
Unbalanced current, phase failure, reverse power, harmonic over-limit protection, covering all abnormal working conditions of the motor.
V. Monitoring and Control Functions
1. Operating Parameter Monitoring
Real-time monitoring of parameters such as three-phase current, voltage, power, power factor, frequency, temperature, running time, and start-up times. Measurement accuracy ±1%.
2. Power Quality Analysis
Built-in harmonic analysis function, monitoring of voltage/current harmonic distortion rate, supporting harmonic over-limit alarm, suitable for non-linear load conditions such as inverters and soft starters.
3. Events and Fault Records
Stores up to hundreds of event records (faults, alarms, operations), with timestamps, facilitating troubleshooting, fault causes, action times, and running parameters, making it convenient for operation analysis and equipment diagnosis.
4. Motor Control
Supports local/remote start/stop control, forward/reverse interlock, soft start coordination control, fault automatic reset (programmable), suitable for various motor control logic.
5. Dual Setpoint Switching
Built-in two independent protection parameters that can be quickly switched through external signals or communication instructions, suitable for motor no-load/lit, continuous/intermittent operation and other different modes.
VI. Human-Machine Interface and Configuration
1. Display and Operation
Equipped with a high-resolution LCD display and buttons, allowing on-site viewing of operating parameters, fault information, protection set values, supporting on-site parameter configuration and function debugging.
2. Configuration Method
Local Configuration: Parameter settings through panel buttons and LCD
Remote Configuration: Connecting to the upper computer software through communication interface to achieve remote parameter configuration, firmware upgrade, data monitoring
VII. Communication and System Integration
Supports Modbus RTU, Profibus-DP industrial communication protocols, can be seamlessly integrated with PLC, SCADA, DCS systems, enabling remote monitoring, parameter modification, fault upload, data recording, suitable for large-scale automation control system architectures.
VIII. Application Scenarios
Petrochemical Industry: Key motors such as pumps, compressors, fans, mixers
Electric Power Industry: Auxiliary motor of power plants, cooling tower fans, water supply pump motors protection
Mining Industry: Conveyor belts, crushers, elevators, etc., heavy-load motor protection
Water Treatment: Water pumps, aeration fans, mixing machines motor protection
Industrial Manufacturing: Machine tools, injection molding machines, textile machinery, etc., equipment motor protection
Get a Quote