Honeywell 51309118-225 (MC-TDIY22 Digital Input FTA)
Description
I. Product Introduction
51309118‑225 (Model MC‑TDIY22) is a 16-channel digital input FTA (Field Terminal Board) for the Honeywell UCN/Experion PKS/TDC3000 system, specifically equipped with MU‑PDIY22/MC‑PDIY22 (DI IOP) digital input cards. It has no anti-corrosion coating, CE compliance, and is used in dry, non-corrosive control rooms to collect 24VDC/120VAC switch quantity signals.
II. Model Interpretation
51309118‑225: Honeywell material code, the last ‑225 indicates no anti-corrosion coating + CE certification + standard terminals.
MC‑TDIY22: Product model, MC = module prefix, TDIY = Digital Input, 22 = sub-model; FTA = Field Terminal Board.
Same series: 51309118‑175 is the **version with anti-corrosion coating (CC)**, suitable for harsh conditions.
III. Technical Parameters
Channel Quantity: 16 digital input channels (single-ended).
Input Signals: 24VDC (dry contact / wet contact), 120VAC, compatible with buttons, limit switches, relay contacts.
Terminal Type: Red compression terminals (Compression), resistant to vibration, reliable connection.
Isolation Characteristics: Electrical isolation between channels, between the field and the system side at 2500 VAC, anti-surge and common-mode interference.
Coating: No anti-corrosion coating (non‑CC), only applicable to dry environments.
Compliance Certification: CE certification (EMC/LVD Directive).
Operating Environment: Temperature ‑20 ℃ to +60 ℃, humidity 5%–95% without condensation; prohibited in damp / dust / corrosive environments.
Mechanical Dimensions: 6 inches (152 mm) Size A standard DCS card.
Weight: Approximately 0.65 kg.
Redundancy Support: Non-redundant, redundancy requires two FTA + two IOP.
IV. Interface and Communication Configuration
Field Side: 16 compression terminals, connected to switches / relays / contacts, single-ended grounding of the shielding layer.
System Side: Special high-density connector, directly connected to MU‑PDIY22/MC‑PDIY22 IOP card.
Communication: Relying on IOP card to access UCN network, supports remote configuration, diagnosis, and fault upload.
V. Core Functions
Signal Conversion: 16 centralized wiring, simplifies cabinet wiring, facilitates maintenance.
Signal Conditioning: Board-mounted filtering + isolation, suppresses EMI/RFI, ensures stable switch quantity collection.
Line Protection: Overcurrent / overvoltage protection, blocks abnormal signals from the field, protects IOP card.
Fault Diagnosis: Channel open / short circuit detection, fault information uploaded to the upper computer.
Hot Swap: Supports online replacement, does not affect system operation, shortens downtime.
VI. Application Scenarios
Petrochemicals, power, water treatment: Switch quantity collection in conventional control rooms (pump / valve status, limit switches, alarm contacts).
Honeywell TDC3000/Experion PKS: Paired with MU‑PDIY22/MC‑PDIY22 to build a high-density digital input system.
Environmental Limitations: Only applicable to dry, dust-free, and non-corrosive gas control rooms, not for outdoor or humid sites.
VII. Usage and Maintenance Instructions Instruction Manual
Installation: Insert into the standard Size A rack slot and lock it in place with the IOP card; supports hot swapping.
Wiring: Connect the positive and negative terminals of the contacts to the corresponding terminals, and press them firmly; single-ended grounding of the shielded wire to avoid circulating current.
Configuration: Configure the channel type (24VDC/120VAC) and debounce time on the engineer station, and it can be collected after downloading.
Maintenance instructions
Regular inspection: Check the terminal tightening every quarter, ensure there is no oxidation on the wiring, and ensure the connectors are in good contact.
Environmental maintenance: Keep the cabinet dry and dust-free, with a temperature range of -20 ℃ to +60 ℃, and keep away from strong electromagnetic interference.
Fault handling: First check the wiring / grounding for abnormal signals, then check the connection between the connector and the IOP card; if damaged, it can be replaced online.
Storage: Store the spare board cards in a cool and dry place, with a temperature range of -40 ℃ to +85 ℃, avoiding heavy pressure and vibration.
Note: Without anti-corrosion coating, it is strictly prohibited to use in a humid / corrosive environment for a long time.
Get a Quote