Honeywell 51304640‑175 (51304640175)
Description
Technical Specifications
Part Number: 51304640‑175 (51304640175)
Alternative ID: MU‑GDID17, 32‑Ch DI FTA, GI/IS, 24VDC, Galvanic Isolator, CC, CE
Module Type: Field Termination Assembly (FTA), Digital Input Isolation (GI/IS)
System Compatibility: Honeywell UCN, TDC3000, TPS, C300 Controller, Experion PKS
Input Channels: 32 isolated channels (24 VDC, sink/source configurable, dry contact or wet 24 VDC)
Isolation Rating: 1500 VAC (channel‑to‑backplane), optical isolation per channel; IS‑rated for hazardous areas (Class I, Div. 2)
Input Voltage: 24 VDC ±10% (field side); 5 VDC (backplane logic)
Input Current: 10 mA nominal per channel (on‑state)
Response Time: <10 ms per channel (typical)
Diagnostics: Channel‑level status LEDs; remote fault logging via UCN/C300
Power: 24 VDC ±10%, 200 mA (external or backplane‑fed)
Operating Temperature: 0°C to +60°C (GI/IS‑rated; conformal coated for harsh environments)
Storage Temperature: ‑40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 152 × 178 × 25 mm (7‑inch FTA, high‑density)
Weight: ~0.45 kg
Coating: Conformal coated (harsh environment grade, CC)
Certifications: CE, RoHS, UL 508, ATEX/IECEx (IS‑compliant)
Revisions: Common Rev J (hardware/firmware, CC/IS‑enhanced)
Status: Active (new surplus/repair available; backward compatible with 51304640‑125/225/325/375)
Interface & Communication Configuration
Host Interface: UCN/TDC3000/C300 backplane (proprietary, 1 Mbps I/O Link)
Field Interface: 32 × screw terminals (GI/IS‑rated, isolated per channel, 24 VDC common)
Protocol Support: UCN digital input protocol; compatible with all Honeywell UCN/C300 digital controllers
Diagnostics: 32 channel LEDs (On/Off); 2 global LEDs (Power, Fault); remote alarm via UCN/C300
Hot Swap: Yes (replace without system shutdown; auto‑reconnect in <5 seconds)
Compatibility: Drop‑in replacement for 51304640‑125/225/325/375; works with MU‑GAOX12, MC‑TAIH15, and other UCN FTAs; non‑redundant design
Core Functions
High‑Density Input: 32‑channel digital input saves cabinet space for large I/O systems.
GI/IS Dual Rating: Suitable for both general industrial and hazardous area (intrinsically safe) installations.
24 VDC Galvanic Isolation: Optical isolation protects system from field noise, voltage spikes, and ground loops.
Harsh Environment Protection: Conformal coating (CC) safeguards against dust, moisture, and chemical vapors.
Wide Signal Compatibility: Accepts dry contact closures or wet 24 VDC signals from switches, pushbuttons, and sensors.
Channel‑Level Diagnostics: Individual LEDs enable quick fault isolation; remote monitoring enhances maintainability.
Application Scenarios
General & Hazardous Industrial Control: Manufacturing, food & beverage, water treatment, and power facilities (non‑hazardous and Class I, Div. 2 hazardous areas).
High‑I/O Density Monitoring: Large‑scale discrete signal monitoring (limit switches, level sensors, pushbuttons).
24 VDC Signal Systems: Facilities using standard 24 VDC field devices for digital input.
Harsh Environment & Hazardous Area Upgrades: Conformal‑coated and IS‑rated design for dusty, humid, or explosive environments.
Compatibility Note
System Compatibility: Honeywell UCN, TDC3000, TPS, C300 Controller, Experion PKS (requires UCN/C300 digital controller card)
Replacement Cross‑Reference:
51304640‑125: 32‑ch, GI, 0–60°C, screw terminals, CE, non‑CC
51304640‑175: 32‑ch, GI/IS, 0–60°C, screw terminals, CE, CC
51304640‑225: 16‑ch, GI, 0–60°C, screw terminals, CE, non‑CC
51304640‑325: 32‑ch, GI/IS, 0–60°C, crimp terminals, CE, non‑CC
51304640‑375: 32‑ch, GI/IS, 0–60°C, crimp terminals, CE, CC
Key Difference (175 vs 125): The 175 adds intrinsic safety (IS) rating and conformal coating (CC) for hazardous and harsh environments, while the 125 is basic GI‑only.