Honeywell 51304640‑175 (51304640175)
May 28, 2026

Honeywell 51304640‑175 (51304640175)

Product Introduction Model: 51304640‑175 (Alias: 51304640175, MU‑GDID17, 32‑Ch Digital Input FTA, GI/IS, 24VDC, CC, CE) Type: 32‑Channel Digital Input Field Termination Assembly (FTA, General/Intrinsically Safe Interface, Conformal Coated) Manufacturer: Honeywell Series: TDC3000 / TPS / UCN DCS & C300/Experion PKS Description: The 51304640‑175 is a high‑density, conformal‑coated digital input FTA for Honeywell UCN/TDC3000/TPS and C300/Experion PKS. It provides 32 channels of optically isolated 24 VDC digital input for switch/sensor contacts, supporting both general industrial (GI) and intrinsic safety (IS) applications with harsh‑environment conformal coating。

Description

Technical Specifications

  • Part Number: 51304640‑175 (51304640175)

  • Alternative ID: MU‑GDID17, 32‑Ch DI FTA, GI/IS, 24VDC, Galvanic Isolator, CC, CE

  • Module Type: Field Termination Assembly (FTA), Digital Input Isolation (GI/IS)

  • System Compatibility: Honeywell UCN, TDC3000, TPS, C300 Controller, Experion PKS

  • Input Channels: 32 isolated channels (24 VDC, sink/source configurable, dry contact or wet 24 VDC)

  • Isolation Rating: 1500 VAC (channel‑to‑backplane), optical isolation per channel; IS‑rated for hazardous areas (Class I, Div. 2)

  • Input Voltage: 24 VDC ±10% (field side); 5 VDC (backplane logic)

  • Input Current: 10 mA nominal per channel (on‑state)

  • Response Time: <10 ms per channel (typical)

  • Diagnostics: Channel‑level status LEDs; remote fault logging via UCN/C300

  • Power: 24 VDC ±10%, 200 mA (external or backplane‑fed)

  • Operating Temperature: 0°C to +60°C (GI/IS‑rated; conformal coated for harsh environments)

  • Storage Temperature: ‑40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Dimensions (H×W×D): 152 × 178 × 25 mm (7‑inch FTA, high‑density)

  • Weight: ~0.45 kg

  • Coating: Conformal coated (harsh environment grade, CC)

  • Certifications: CE, RoHS, UL 508, ATEX/IECEx (IS‑compliant)

  • Revisions: Common Rev J (hardware/firmware, CC/IS‑enhanced)

  • Status: Active (new surplus/repair available; backward compatible with 51304640‑125/225/325/375)

Interface & Communication Configuration

  • Host Interface: UCN/TDC3000/C300 backplane (proprietary, 1 Mbps I/O Link)

  • Field Interface: 32 × screw terminals (GI/IS‑rated, isolated per channel, 24 VDC common)

  • Protocol Support: UCN digital input protocol; compatible with all Honeywell UCN/C300 digital controllers

  • Diagnostics: 32 channel LEDs (On/Off); 2 global LEDs (Power, Fault); remote alarm via UCN/C300

  • Hot Swap: Yes (replace without system shutdown; auto‑reconnect in <5 seconds)

  • Compatibility: Drop‑in replacement for 51304640‑125/225/325/375; works with MU‑GAOX12, MC‑TAIH15, and other UCN FTAs; non‑redundant design

Core Functions

  1. High‑Density Input: 32‑channel digital input saves cabinet space for large I/O systems.

  2. GI/IS Dual Rating: Suitable for both general industrial and hazardous area (intrinsically safe) installations.

  3. 24 VDC Galvanic Isolation: Optical isolation protects system from field noise, voltage spikes, and ground loops.

  4. Harsh Environment Protection: Conformal coating (CC) safeguards against dust, moisture, and chemical vapors.

  5. Wide Signal Compatibility: Accepts dry contact closures or wet 24 VDC signals from switches, pushbuttons, and sensors.

  6. Channel‑Level Diagnostics: Individual LEDs enable quick fault isolation; remote monitoring enhances maintainability.

Application Scenarios

  • General & Hazardous Industrial Control: Manufacturing, food & beverage, water treatment, and power facilities (non‑hazardous and Class I, Div. 2 hazardous areas).

  • High‑I/O Density Monitoring: Large‑scale discrete signal monitoring (limit switches, level sensors, pushbuttons).

  • 24 VDC Signal Systems: Facilities using standard 24 VDC field devices for digital input.

  • Harsh Environment & Hazardous Area Upgrades: Conformal‑coated and IS‑rated design for dusty, humid, or explosive environments.

Compatibility Note

  • System Compatibility: Honeywell UCN, TDC3000, TPS, C300 Controller, Experion PKS (requires UCN/C300 digital controller card)

  • Replacement Cross‑Reference:

    • 51304640‑125: 32‑ch, GI, 0–60°C, screw terminals, CE, non‑CC

    • 51304640‑175: 32‑ch, GI/IS, 0–60°C, screw terminals, CE, CC

    • 51304640‑225: 16‑ch, GI, 0–60°C, screw terminals, CE, non‑CC

    • 51304640‑325: 32‑ch, GI/IS, 0–60°C, crimp terminals, CE, non‑CC

    • 51304640‑375: 32‑ch, GI/IS, 0–60°C, crimp terminals, CE, CC

  • Key Difference (175 vs 125): The 175 adds intrinsic safety (IS) rating and conformal coating (CC) for hazardous and harsh environments, while the 125 is basic GI‑only.


Get a Quote