Honeywell 51304638‑375 (51304638375)
Description
Technical Specifications
Part Number: 51304638‑375 (51304638375)
Alternative ID: MC‑GAOX72, 12‑Ch AO FTA, GI, CE, CC, Non‑Redundant, Crimp
Module Type: Field Terminal Assembly (FTA), Analog Output Isolation (GI)
System Compatibility: Honeywell UCN, TDC3000, TPS, C300 Controller (LCN & UCN networks)
Output Channels: 12 isolated channels (4‑20 mA DC or 0‑10 VDC, sink/source configurable)
Isolation Rating: 1500 VAC (channel‑to‑backplane), 2500 VAC surge immunity
Resolution: 12‑bit (0.025% of full scale)
Accuracy: ±0.05% FS @ 25°C; ±0.1% FS over temperature range
Update Rate: 10 ms per channel
Load Resistance: 0–600 Ω (4‑20 mA); 0–10 kΩ (0‑10 VDC)
Power: 24 VDC ±10%, 180 mA (external or backplane‑fed)
Power Consumption: ~4.3 W
Operating Temperature: 0°C to +60°C (industrial standard, GI‑rated)
Storage Temperature: ‑40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 152 × 178 × 25 mm (7‑inch FTA, high‑density)
Weight: ~0.40 kg
Coating: Conformal coated (harsh environment grade, CC)
Certifications: CE, RoHS, UL 508 compliant
Revisions: Common Rev S (hardware/firmware, CC‑enhanced)
Status: Active (new surplus/repair available; backward compatible with 51304638‑100/125/175/325/600)
Interface & Communication Configuration
Host Interface: UCN/TDC3000/C300 backplane (proprietary, 1 Mbps)
Field Interface: 12 × crimp‑style screw terminals (GI‑rated, isolated per channel)
Protocol Support: UCN analog output protocol; compatible with all Honeywell UCN/C300 analog controllers
Diagnostics: 2 on‑board LEDs (Power, Fault); remote alarm via UCN/C300; channel‑specific fault logging (open/short circuit)
Hot Swap: Yes (replace without system shutdown; auto‑reconnect in <5 seconds)
Compatibility: Drop‑in replacement for 51304638‑100/125/175/325/600; works with MC‑TAIH15, MC‑TDID72, and other UCN FTAs; non‑redundant design
Core Functions
High‑Density Isolation: 12‑channel galvanic isolation saves cabinet space for large I/O systems.
Dual‑Signal Output: Configurable for 4‑20 mA (current) or 0‑10 VDC (voltage) to support diverse field devices.
Harsh Environment Protection: Conformal coating (CC) safeguards against dust, moisture, and chemical vapors.
GI‑Rated Crimp Terminals: Simplify wiring for general industrial applications (non‑hazardous areas).
Fault Protection & Diagnostics: Isolates channel faults; LED and remote alarm monitoring enhance system reliability.
Application Scenarios
General Industrial Process Control: Manufacturing, food & beverage, and water treatment facilities (non‑hazardous areas).
High‑I/O Density Loops: Large‑scale flow, pressure, temperature, and level control requiring 12 analog outputs.
Mixed Signal Systems: Facilities using both 4‑20 mA valves/actuators and 0‑10 VDC VFDs/indicators.
Harsh Environment Upgrades: Conformal‑coated design for dusty, humid, or chemically aggressive environments.
Compatibility Note
System Compatibility: Honeywell UCN, TDC3000, TPS, C300 Controller (requires UCN/C300 analog controller card)
Replacement Cross‑Reference:
51304638‑100: 8‑ch, standard, 0–55°C, screw terminals
51304638‑125: 8‑ch, enhanced, 0–60°C, screw terminals
51304638‑175: 8‑ch, high‑temp, ‑20°C to +70°C, screw terminals, CC
51304638‑325: 12‑ch, GI/IS, 0–60°C, crimp terminals, ATEX‑rated
51304638‑375: 12‑ch, GI, 0–60°C, crimp terminals, CC, non‑redundant
Key Difference (325 vs 375): The 325 is IS‑rated for hazardous areas; the 375 is GI‑rated with conformal coating for harsh general industrial environments.