Honeywell 51304638‑175 (51304638175)
Description
Technical Specifications
Part Number: 51304638‑175 (51304638175)
Alternative ID: MC‑GAOX02, Analog Output FTA, High‑Temp 8‑Ch 4‑20 mA Isolator
Module Type: Field Terminal Assembly (FTA), Analog Output Isolation
System Compatibility: Honeywell UCN, TDC3000, TPS (LCN & UCN networks)
Output Channels: 8 isolated channels (4‑20 mA DC, sink/source configurable)
Isolation Rating: 1500 VAC (channel‑to‑backplane), 2500 VAC surge immunity
Resolution: 12‑bit (0.025% of full scale)
Accuracy: ±0.05% FS @ 25°C; ±0.1% FS over temperature range
Update Rate: 10 ms per channel
Load Resistance: 0–600 Ω (per channel)
Power: 24 VDC ±10%, 150 mA (external or backplane‑fed)
Power Consumption: ~3.6 W
Operating Temperature: ‑20°C to +70°C (high‑temperature variant)
Storage Temperature: ‑40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 152 × 127 × 25 mm (6‑inch FTA)
Weight: ~0.30 kg
Coating: Conformal coated (harsh environment grade)
Certifications: CE, RoHS, UL 508 compliant
Revisions: Common Rev S (hardware/firmware)
Status: Active (new surplus/repair available; backward compatible with 51304638‑100/125/600)
Interface & Communication Configuration
Host Interface: UCN/TDC3000 backplane (proprietary, 1 Mbps)
Field Interface: 8 × screw terminals (4‑20 mA, isolated per channel)
Protocol Support: UCN analog output protocol; compatible with all Honeywell UCN analog controllers
Diagnostics: 2 on‑board LEDs (Power, Fault); remote alarm via UCN; channel‑specific fault logging (open/short circuit)
Hot Swap: Yes (replace without system shutdown; auto‑reconnect in <5 seconds)
Compatibility: Drop‑in replacement for 51304638‑100/125/600; works with MC‑TAIH15, MC‑TDID72, and other UCN FTAs
Core Functions
High‑Temperature Isolation: 8‑channel galvanic isolation operates reliably from ‑20°C to +70°C, ideal for extreme environments.
Signal Conditioning: Converts UCN controller digital signals to precision 4‑20 mA analog outputs for valves, actuators, and VFDs.
Fault Protection: Isolates channel faults (open/short) from the backplane; surge protection prevents damage from lightning or switching transients.
High‑Accuracy Control: 12‑bit resolution and ±0.05% FS accuracy ensure precise process control in critical loops.
Harsh Environment Reliability: Conformal coating and wide temperature range suit chemical, petrochemical, and power generation facilities.
Application Scenarios
High‑Temperature Process Areas: Refineries, furnaces, and industrial ovens (‑20°C to +70°C operation).
Process Control Loops: Regulating flow, pressure, temperature, and level via 4‑20 mA control valves and actuators.
Motor Control: Driving variable‑frequency drives (VFDs) for pump/fan speed control in noisy industrial environments.
Legacy System Upgrades: Isolating modern UCN controllers from older, ungrounded field devices in TDC3000/TPS upgrades.
Compatibility Note
System Compatibility: Honeywell UCN, TDC3000, TPS (requires UCN analog controller card)
Replacement Cross‑Reference:
51304638‑100: Standard isolation, 0–55°C
51304638‑125: Enhanced isolation, 0–60°C, Rev S firmware
51304638‑175: High‑temperature variant, ‑20°C to +70°C, Rev S firmware
51304638‑600: 8‑channel, high‑surge (3000 VAC) version
Key Difference (125 vs 175): The 175 revision extends operating temperature to ‑20°C to +70°C (vs 0–60°C for 125), making it suitable for colder or hotter industrial environments.