Honeywell 51304584‑300 (51304584300)
Description
Technical Specifications
Part Number: 51304584‑300 (51304584300)
Alternative ID: EPDGP I/O Card, EXCH IO Board, Peripheral Gateway Interface Module
Module Type: Peripheral Gateway I/O Interface (EPDGP/EPDG2 Compatible)
System Compatibility: Honeywell TDC3000 / TPS (LCN network, EPDGP/EPDG2 gateway nodes)
Processor: On‑board 16‑bit microcontroller (hardened ESD/EMI protection)
Memory: 128 KB RAM, 256 KB Flash (firmware, field‑upgradable)
Host Interface: LCN (1 Mbps, electrical, BNC 75Ω)
Peripheral Interface: 3 × DB‑25 ports (RS‑232/RS‑485 software‑configurable)
I/O Channels: 16 digital points (8DI/8DO, fully isolated, 24 VDC field‑side)
Output Type: Solid‑state transistor outputs (300 mA max per channel, short‑circuit protected)
Isolation: 1500 VAC (channel‑to‑backplane), 3000 VAC surge immunity
Power: 5 VDC ±5%, 450 mA (from backplane)
Power Consumption: ~2.25 W
Operating Temperature: ‑40°C to +85°C (full industrial range)
Storage Temperature: ‑40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 178 × 127 × 25 mm
Weight: ~0.25 kg
Coating: Conformal coated (harsh environment grade, chemical/solvent resistant)
Certifications: CE, RoHS, UL 508, CSA compliant
Revisions: Common Rev H (hardware/firmware)
Status: Active (Current Production); direct replacement for 51304584‑100/200.
Interface & Communication Configuration
Host Interface: LCN electrical (BNC, 75Ω) – connects to TDC3000/TPS LCN network
Peripheral Ports: 3 × DB‑25 (RS‑232: up to 115.2 kbps; RS‑485: multi‑drop up to 1 Mbps, 32 nodes max)
Protocol Support: LCN (proprietary); Modbus RTU, ASCII, DF1, Allen‑Bradley DF1, Siemens 3964R
Diagnostics: 3 on‑board LEDs (Power, LCN Link, Peripheral Comm); remote alarm reporting via LCN; enhanced BIST (built‑in self‑test); fault logging with timestamp
Hot Swap: Yes (replace without system shutdown; LCN auto‑reconnect in <10 seconds)
Compatibility: Fully interoperable with EPDGP/EPDG2 gateways; backward compatible with 51304584‑100/200 (drop‑in replacement); works with LCN A/B interface boards (51304542/44 series)
Core Functions
EPDGP Gateway Interface: High‑speed I/O and communication hub for EPDGP/EPDG2 peripheral gateways.
Protocol Conversion: Translates LCN proprietary protocol to industry‑standard protocols for third‑party PLCs, HMIs, and legacy subsystems.
Digital I/O Control: 16 fully isolated digital points (8DI/8DO) for direct interfacing with 24 VDC field devices (sensors, relays, contactors, motor starters).
Data Buffering & Routing: 128 KB RAM ensures reliable data transmission during network fluctuations; priority‑based data handling for critical I/O.
Extreme Environment Reliability: Full industrial temperature range (‑40°C to +85°C) and 3000 VAC surge immunity protect against electrical noise, voltage spikes, and harsh conditions.
Enhanced Diagnostics & Maintenance: Advanced fault logging and BIST reduce downtime; field‑upgradable firmware eliminates need for hardware replacement.
Application Scenarios
TDC3000/TPS DCS Integration: Connecting third‑party PLCs (Siemens, Allen‑Bradley, Schneider), custom peripherals, or legacy systems via EPDGP/EPDG2 gateways.
Process Automation: Chemical, petrochemical, oil & gas, power generation, pulp & paper (multi‑vendor system integration in high‑noise, extreme‑temperature areas).
Harsh Industrial Environments: Freezing (‑40°C) to high‑heat (+85°C) facilities; dusty, humid, or corrosive environments (conformal coated).
Legacy System Upgrades: Direct, drop‑in replacement for aging 51304584‑100/200 boards in existing TDC3000/TPS installations; no system reconfiguration required.
Compatibility Note
System Compatibility: Honeywell TDC3000/TPS (requires EPDGP/EPDG2 gateway node; LCN network mandatory)
Replacement: 51304584‑100 → 51304584‑200 → 51304584‑300 (current production)
Firmware: Requires TDC3000 firmware Rev 300+ and EPDGP firmware Rev 150+ for full functionality
Key Differences (100/200/300):
51304584‑100: ‑20°C to +70°C, basic surge protection (1500 VAC)
51304584‑200: ‑25°C to +75°C, enhanced surge protection (2500 VAC)
51304584‑300: ‑40°C to +85°C, maximum surge protection (3000 VAC), chemical‑resistant coating, Rev H firmware.
Get a Quote