Honeywell 51304584‑100 (51304584100)
Description
Technical Specifications
Part Number: 51304584‑100 (51304584100)
Alternative ID: EPDGP Board, EXCH IO Card, Peripheral Interface Module
Module Type: Peripheral Gateway I/O Interface (EPDGP/EPDG2)
System Compatibility: Honeywell TDC3000 / TPS (LCN network, EPDGP/EPDG2 gateways)
Processor: On‑board 16‑bit microcontroller
Memory: 128 KB RAM, 256 KB Flash (firmware)
Host Interface: LCN (1 Mbps, electrical, BNC 75Ω)
Peripheral Interface: 3 × DB‑25 ports (RS‑232/RS‑485 configurable)
I/O Channels: 16 digital points (8 input / 8 output, configurable)
Input Voltage: 24 VDC (field‑side)
Output Type: Solid‑state transistor outputs
Isolation: 1500 VAC (channel‑to‑backplane)
Power: 5 VDC ±5%, 400 mA (from backplane)
Power Consumption: ~2 W
Operating Temperature: -20°C to +70°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 178 × 127 × 25 mm
Weight: ~0.18 kg
Coating: Conformal coated (for harsh environments)
Certifications: CE, RoHS compliant
Revisions: Common Rev G (hardware/firmware)
Status: Discontinued (replaced by updated EPDGP interface module)
Interface & Communication Configuration
Host Interface: LCN electrical (BNC, 75Ω) – connects to TDC3000/TPS LCN network
Peripheral Ports: 3 × DB‑25 (RS‑232 for point‑to‑point; RS‑485 for multi‑drop, up to 1 Mbps)
Protocol Support: LCN (proprietary); Modbus RTU, ASCII, DF1 (peripheral side)
Diagnostics: 3 on‑board LEDs (Power, LCN Link, Peripheral Comm); remote alarm reporting via LCN
Hot Swap: Yes (replace without system shutdown)
Compatibility: Works with EPDGP and EPDG2 gateway nodes; interoperable with LCN A/B interface boards (51304542/44 series)
Core Functions
EPDGP Gateway Interface: Dedicated I/O and communication board for EPDGP/EPDG2 peripheral gateways.
Protocol Conversion: Translates LCN proprietary protocol to industry‑standard protocols (Modbus RTU, ASCII) for external subsystems.
Digital I/O Control: Provides 16 configurable digital points (8DI/8DO) for direct field device interfacing.
Data Buffering & Routing: Buffers high‑volume data between LCN and peripherals, ensuring reliable transmission.
Fault Isolation & Diagnostics: Isolates peripheral communication faults from the LCN; provides real‑time status monitoring.
Application Scenarios
TDC3000/TPS DCS: Integrating third‑party PLCs, custom peripherals, or legacy systems via EPDGP/EPDG2 gateways.
Process Automation: Chemical, petrochemical, oil & gas, power generation (multi‑vendor system integration).
Legacy System Upgrades: Connecting older external controllers to modern TDC3000/TPS installations.
Harsh Industrial Environments: Conformal coating and wide temperature range suit high‑noise, dusty, or extreme‑temperature areas.
Compatibility Note
System Compatibility: Honeywell TDC3000/TPS (requires EPDGP/EPDG2 gateway node)
Replacement: 51304584‑100 → Updated EPDGP interface module (current part number varies by revision)
Firmware: Requires TDC3000 firmware Rev 300+ and EPDGP firmware Rev 150+ for full functionality
Key Difference: 51304584‑100 = EPDGP peripheral gateway I/O board; 51304542/44 series = LCN A/B cable interface boards (for remote I/O panels)